Appendix B Default Configuration Settings
GSC400’s are factory programmed and shipped with default settings loaded into the
controller. These are the defaults of the settings located in the Advanced Setup Menu.
Table 27 – GSC400 Default Settings
FUNCTION
DEFAULT SETTINGS
J1939
Manufacturer
John Deere
Display Group 1
Disable
Display Group 2
Disable
DTC Display
Disable
Active DTC Log
Disable
Read Stored DTC
Disable
Auto Power ECM
Disable
ECM Power Delay
6 seconds
Cummins Idle
Disable
SPN Conversion
Version 3
EMS2B Freq Sel
Primary
EMS2B Acc Pedal
50%
High Engine Temp
Input Pin
Analog2 – Low Z
Signal Source
Dat Pin2 (Sender2)
Bypass Delay
30 Seconds
Switch Setting
SW Closed = Fail
Shorted Sender
Disable
Open Sender
Disable
Units
Fahrenheit
Warning Level
200°F
Failure Level
220°F
Oil Pressure
Input Pin
Analog3 – Low Z
Signal Source
Datcon 1
Bypass Delay
30 Seconds
Switch Setting
SW Closed = Fail
Shorted Sender
Disable
Open Sender
Disable
Units
PSI
Warning Level
20 PSI
Failure Level
15 PSI
Fuel Level
Input Pin
Disabled
Signal Source
Switch
Bypass Delay
30 Seconds
Switch Setting
SW Closed = Fail
Shorted Sender
Disable
Open Sender
Disable
Units
Percentage
Warning Level
25%
Failure Level
5%