User manual
109 of 148
Digital Output Setup
All selections apply
to each individual
output
Extra Relay
Disable, Warm-Up, ETS,
Output A
Glowplug, Cooldown,
Output B
Over Crank , High Temp Fail ,
Output C
High Temp warn, Low Oil Fail ,
Output D
Low Oil Warning, Under RPM Fail,
Output E
Under RPM Warn, Over RPM Fail
Output F
Over RPM Warn, Low Fuel Fail
Output G
Low Fuel Warn, Battery Fail,
Output H
Battery Warn, Low Coolant Fail,
Low Coolant warn, Not in Auto,
Failure, Crank Rest, Engine Running, Crank On, Exerciser
Alarm, Recharge Alarm, Under Volt Warn, Over volt warn,
Over Amp Warn, Fuel in Basin, Volt Regulator, Low Temp
Warn, Back Light, Auxiliary Warn, Maintenance, System
Ready, Common Output 1, Common Output 2, Dummy Loads,
High Fuel Warn, Current Latch, Config Warn 1, Config Warn 2,
Config Fail 1, Config Fail 2, Engine Fan, Low AuxA1 Warn,
Low AuxA1 Fail, High AuxA1 Warn, High AuxA1 Fail, Low
AuxA2 Warn, Low AuxA2 Fail, High AuxA2 Warn, High AuxA2
Fail.
Exerciser setup
Exerciser Enable
Disable, enable
Run Duration
10-240 minutes
Pre-Alarm Delay
1-20 minutes
Repeat Freq.
1-672 hours
Start Hour
0-23
Start Date
1-31
Digital Input Setup
Input A (Bat)
Disable, Low Air Pres
Low Hyd Pres, Low Oil Pres,
EPS Supply Load
Alarm Silence, Low Coolant,
Volt Select 1, Volt Select 2,
Idle Mode, Start/Stop,
Auxiliary Fail, Auxiliary Warn,
Charger Fault1, Charger Fault2,
High Fuel Warn, Config Warn 1,
Config Warn 2, Config Fail 1,
Config Fail 2, Start Inhibit
(located at bottom of menu)
Global Trig, Crank Trig, Run Trig,
Crank+Run Trig,
Input B (Bat)
Input C (Bat)
Input D (Bat)
Input E (Gnd)
Input F (Gnd)
Input G (Gnd)
Input H (Gnd)
Battery Setup
Low Auto Charge
Disable, Enable
Charge Pre-Alarm
1-60 minutes
Charge Duration
10-240 minutes
Recharge Level
7-24 volts
Low Warn Level
7-24 volts
Low Fail Level
7-24 volts
High Warn Level
12-32 volts
High Fail Level
12-32 volts
Low Vol InCrank
4 – 18 volts