Open Sender
Disable, Warning, Shutdown
Units
Percentage
Warning Level
0-90%
Failure Level
0-90%
0% Fuel Level
0-1000 Ohms
25% Fuel Level
0-1000 Ohms
50% Fuel Level
0-1000 Ohms
75% Fuel Level
0-1000 Ohms
100% Fuel Level
0-1000 Ohms
Oil Level
Input Pin
Reserve, Analog 2-7
Signal Source
J1939, Switch input, Sender
Bypass Delay
10-60 Seconds
Switch Setting
GND = Fail, Open = Fail
Shorted Sender
Disable, Warning, Shutdown
Open Sender
Disable, Warning, Shutdown
Units
Percentage
Warning Level
0-100%
Failure Level
0-100%
Fuel In Basin
Input Pin
Reserve, Analog 2-7
Signal Source
J1939, Switch input, Sender
Bypass Delay
10-60 Seconds
Switch Setting
GND = Fail, Open = Fail
Shorted Sender
Disable, Warning, Shutdown
Open Sender
Disable, Warning, Shutdown
Units
Percentage
Warning Level
0-90%
Failure Level
0-90%
Low Engine Tmp
Input Pin
Reserve, Analog 2-7
Signal Source
J1939, Switch input, Sender
Bypass Delay
10-60 Seconds
Switch Setting
GND = Fail, Open = Fail
Shorted Sender
Disable, Warning, Shutdown
Open Sender
Disable, Warning, Shutdown
Units
Fahrenheit, Celsius
Warning Level
10-265°F, 10-265°C
Aux Analog 1
Input Pin
Reserve, Analog 2-7
Signal Source
Switch Input, Sender Input
Bypass Delay
10-60 Seconds
Switch Setting
Closed = Fail, Open = Fail
Shorted Sender
Disable, Warning, Shutdown
Open Sender
Disable, Warning, Shutdown
Temp Units
Fahrenheit, Celsius
Temp High Warn
10-265°F, 10-265°C
Temp High Fail
10-265°F, 10-265°C
Temp Low Warn
10-265°F, 10-265°C
Temp Low Fail
10-265°F, 10-265°C
Pres Units
PSI, kPa
Pres High Warn
0 – 700PSI, 0 – 700 kPa
Pres High Fail
0 – 700PSI, 0 – 700 kPa
Pres Low Warn
0 – 700PSI, 0 – 700 kPa