Appendix A GSC400 Detailed Advanced Menu Layout
Table 26 – Submenus of the Advanced Menu
Main Menu
Sub Menu
Selections
J1939 Setup
Manufacturer
John Deere, Volvo, Cummins,
Yanmar, Detroit Diesel, Others,
Volvo EMS2B, Isuzu, GM PSI
Loss of ECM
Enable, Disable
Display Group 1
Enable, Disable
Display Group 2
Enable, Disable
DTC Display
Disable, Enable
Active DTC Log
Disable, Enable
Read Stored DTC
Disable, Enable
Auto Power ECM
Disable, Enable
ECM Power Delay
5-30 seconds
Cummins Idle
Disable, GCP Enable, GC1
Enable
SPN Conversion
Version 1, Version 2, Version 3
EMS2B Freq Sel
Primary, Secondary
EMS2B Acc Pedal
40 - 60%
High Engine Tmp
Input Pin
Disable, Analog 2-7
Signal Source
J1939, Switch input, Sender 1, 2,
or 3
Bypass Delay
10-60 Seconds
Switch Setting
GND = Fail, Open = Fail
Shorted Sender
Disable, Warning, Shutdown
Open Sender
Disable, Warning, Shutdown
Units
Fahrenheit, Celsius
Warning Level
10-265°F, 10-265°C
Failure Level
10-265°F, 10-265°C
Oil Pressure
Input Pin
Reserve, Analog 2-7
Signal Source
J1939, Switch input, Sender 1, 2
or 3
Bypass Delay
10-60 Seconds
Switch Setting
GND = Fail, Open = Fail
Shorted Sender
Disable, Warning, Shutdown
Open Sender
Disable, Warning, Shutdown
Units
PSI, KPa
Warning Level
0-90 PSI, 0-90 KPa
Failure Level
0-90 PSI, 0-90 KPa
Fuel Level
Input Pin
Reserve, Analog 2-7
Signal Source
Switch input, Sender
Bypass Delay
10-60 Seconds
Switch Setting
GND = Warning, OPEN =
Warning, GND = Fail, Open = Fail
Shorted Sender
Disable, Warning, Shutdown