GSC400 Series Automatic Gen-Set Controller Manual Revision 4.1 GSC400 Automatic Gen-Set Controller Installation and User Manual MAN-0076 Rev4.1, GSC400 User Manual.
of 148 Thank You For Purchasing This DynaGen Product Please Read Manual Before Installing Unit Receipt of Shipment and Warranty Return Information Upon receipt of shipment, carefully remove the unit from the shipping container and thoroughly examine the unit for shipping damage. In case of damage, immediately contact the carrier and request that an inspection report be filed prior to contacting DynaGen.
of 148 How to Use this Document Navigating Viewing this Document This document is released in PDF format. Adobe Acrobat Reader is required to view this document. Go to http://get.adobe.com/reader to download the latest version of Acrobat reader. The latest version as of writing is X (version 10.1). Table of Contents Links To jump to a specific document location, hover the mouse icon over the table of contents page number and the mouse icon will change to a pointing hand.
of 148 U VDC Rating Standby Current Operating Temp LCD Operating Temp*** Function Selection Range GSC400 Specifications 12/24 VDC 50 mA @ 12 VDC -40°C to +70°C (-40°F to +158°F) 0 0 0 0 -20 C to 70 C (-4 F to +158 F) 0 0 0 0 -40 C to +70 C (-40 F to +158 F) with heater “-H” option (consult factory) Function Selection Range Speed Sensing Generator pickup 0-300vac, 0-3600rpm Magnetic pickup 0-300vac, 0-3600rpm Voltage Sensing Single phase, 70 - 346vac L-N (600V L-L, LThree phase, L calculated from L-N)
of 148 Abbreviated Table of Contents 1. GSC400 CONTROLLER SERIES -- INTRODUCTION ............................................................... 9 2. INSTALLATION AND WIRING .......................................................................................................13 3. GSC400 CONFIGURATION ...........................................................................................................43 4. OPERATION AND END-USER CONFIGURATION ................................................
of 148 Detailed Table of Contents 1. GSC400 CONTROLLER SERIES -- INTRODUCTION ............................................................... 9 HOW TO USE THIS MANUAL .......................................................................................................10 SAFETY / INFORMATION..............................................................................................................10 RECEIVING, HANDLING, AND STORAGE .....................................................................
of 148 3.7.2 AC Voltage ...........................................................................................................................58 3.7.3 AC Current ...........................................................................................................................62 3.7.2.1 Voltage Select Inputs .............................................................................................................. 61 3.7.3.1 EPS Supplying Load Front Panel Lamp ......................
of 148 D.1 D.2 D.3 D.4 D.5 D.6 GSC400 CONTROLLER HARNESS - ACCESSORIES ................................................................120 GSC400 PROGRAMMER ..........................................................................................................120 CT’S (CURRENT TRANSFORMERS) ..........................................................................................121 SENDERS ................................................................................................................
of 148 1. GSC400 Controller Series -- Introduction 1.1 1.2 1.3 1.4 HOW TO USE THIS MANUAL .......................................................................................................10 SAFETY / INFORMATION..............................................................................................................10 RECEIVING, HANDLING, AND STORAGE .....................................................................................11 GSC400 PRODUCT NUMBER IDENTIFICATION .....................
of 148 1.1 How to Use This Manual This manual is divided into three main sections: 1. Installation and wiring (Section 2) 2. Technician level configuration (Section 3) – this section is meant to be consulted when going through section 2. 3. GSC400 Operation. Day to day end user operation and configuration (Section 4) In addition there are appendixes that contain detailed supplementary information. 1.2 Safety / Information Generator systems contain high voltage circuitry.
of 148 1.3 Receiving, Handling, and Storage Receiving: Every effort is made to ensure that your GSC400 gen-set controller arrives at its destination undamaged and ready for installation. The packaging is designed to protect the GSC400 internal components as well as the enclosure. Care should be taken to protect the equipment from impact at all times. Do not remove the protective packaging until the equipment is at the installation site and ready to be installed.
of 148 1.4 GSC400 Product Number Identification The GSC400 series product numbering scheme (i.e. product number) provides various information – including options selected by the customer – about the unit. A product number has the format given in Figure 1. The product number is located on the backside of the GSC400 controller under the bar code.
of 148 2. Installation and Wiring This section contains information on the wiring of the GSC400 controller. It is meant to be used in conjunction with Section 3 GSC400 Configuration which covers the configuration of the GSC400. 2.1 MOUNTING ..................................................................................................................................13 2.2 GSC400 COMPONENT RATINGS / STANDARDS ........................................................................15 2.
of 148 install the GSC400 in a grounded enclosure. Ensure that the ground wire makes direct contact with the metal in the enclosure; scrape off any paint. Also consider using shielded spark plugs. Isolate the GSC400 enclosure with isolation mounts to prevent excess vibration to the GSC400. It is recommended to limit the maximum average ambient temperature around the GSC400 to 700C to provide headroom. Figure 3 - Dimensions of mounting holes.
of 148 2.2 GSC400 Component Ratings / Standards UL Listing The GSC400 is UL listed to UL508. For conditions of acceptability refer to UL file number: E250327 or contact DynaGen. The conditions of acceptability are also packaged with every unit. U 12V / 24V Operation The GSC400 controller can be placed in either 12V or 24V electrical systems. The user must order the correct GSC400 as 12V operation requires 12V relays and 24V operation requires 24V relays.
2.3 Wiring - Overview This section will explain how to wire your application to the GSC400. Table 1 gives the type and part number for all the mating plugs that plug into the GSC400 terminals. If you do not wish to crimp your own plugs, Table 29 on page 120 gives the part numbers of the various starter-kit harnesses you can order from DynaGen. Only commonly used circuits on each connector are wired. Table 29 lists the circuits (i.e. wires) that are included as part of the harness.
Figure 4 – General GSC400 System Wiring Diagram
of 148 Table 2 – GSC400 Terminal Details PC Config Quick Fit Terminals This is a 10 pin (2x5) connector for the connection of the GSC400 programmer only. This connector is not meant for long term connections under vibration. Terminal Wire Size Current Function (AWG) max.
of 148 Digital Outputs* RS485 (Modbus) AC Voltage Sensing AC Current Sensing J1939 (CAN) Terminal Terminal Wire Size Current Function Detail Location (AWG) max. + V Bat 1 18 1.5A Battery + Output A 2 18 200mA These are sinking outputs (i.e. switched to ground). Output B 3 18 200mA Output C 4 18 200mA Output D 5 18 200mA Output E 6 18 200mA Output F 7 18 200mA Output G 8 18 200mA Output H 9 18 200mA + V Bat 10 18 1.5A Battery + Terminal Terminal Wire Size Current Function Detail Location (AWG) max.
of 148 2.4 Powering the GSC400 and Basic Connections 1 2 3 Engine Logic Battery Logic Extra Relay Logic Menu Location Advanced Setup > Engine Logic Advanced Setup > Battery Setup Advanced Setup > Outputs Setup > Extra Relay Page 47 57 69 There are a group of 8 spade terminals on the back of the GSC400. Their functions are described below.
of 148 Emergency Stop Input Pin 9 of the configurable switched input connector must be grounded (can use pins 11 or 12) to disable the emergency stop feature. When enabled the emergency stop feature forces the controller to remain in the OFF mode and sounds the buzzer. Remote Start Contacts (RSC) A normally open switch needs to be placed across pin 10 of the configurable switch input connector and ground (pin 11 or 12 on the same connector can be used for convenience).
of 148 2.5 Speed Inputs 1 Speed Sensing Menu Location Advanced Setup > Speed Sensing Page 55 The GSC400 senses engine speed via two spade terminals on the bottom of the unit (not needed for J1939). Magnetic input, generator AC voltage, or J1939 can be used. 2.5.1 Generator AC Voltage / Magnetic Pickup Two wires must be run to the speed inputs (even if using generator output).
of 148 This could be caused by the GSC400 speed sensing terminals picking up stray signals during cranking. The speed sensing on the GSC400 is sensitive in order to pick up low voltages during cranking. The GSC400 then thinks the generator has started. Confirm by checking the speed displayed on the controller during cranking (value beside “RPM”). 1. Check that there are no breakers off. This can unload the GSC400 sensing inputs allowing the wiring to act as an antenna. 2.
of 148 2.
of 148 2.6.2 Senders The sensor types Dynagen supports out of the box for engine temperature and oil pressure are given in the following table. Fuel Level, Oil Level, and Fuel in basin types are not supported out of the box; the PC Configurator must be used to store a custom table for these types. Table 4 – Default Senders for Temperature and Oil Pressure Sender Manufacturer and Type Supported Sensing Range Part Number Pins on J2 Datcon High Range 3 and 4 129 to 330 0F High Temp.
of 148 Each sender has a particular pin it is supported on. If your sender part number is not listed in the table or your desired pin is not supported, the PC Configurator can be used to create and store a custom table (refer to manual MAN-0079, the GSC400 PC Interface manual). The GSC400 has Open and Shorted sender diagnostic features. These are disabled by default. The Open Sender Detection will trigger if the analog input voltage rises above 4.76V.
of 148 1. Confirm that the sender is connected to the correct input pin terminal. Check the wiring for continuity. Check that the GSC400 is setup correctly in the advanced menu. 2. With the generator not running, unplug the sensor (analog inputs) plug from the controller. It’s the 2x4 pin connector on the bottom. On the GSC400 sensor terminal, measure the DC voltage of the input pin to battery negative. Do this on the GSC400 terminal, not the plug. It should read 5VDC.
of 148 2.7 AC Voltage / AC Frequency 1 2 AC Voltage AC Frequency Menu Location Advanced Setup > AC Voltage Advanced Setup > AC Frequency Page 58 58 The GSC400 controller requires a neutral reference from the generator. All voltages are measured line to neutral and then converted for display as line to line if required. Battery negative needs to be connected to the neutral of the electrical system as the GSC400 AC voltage sensing requires a battery negative reference.
Figure 5 – GSC400 Three Phase Voltage Configurations
Figure 6 – Three Phase AC Voltage Step down Options
2.8 AC Current 1 AC Current Menu Location Advanced Setup > AC Current Page 62 The GSC400 controller is designed to measure AC current from the generator with the use of current transformers (CTs). CTs with a rating of 5A on the secondary are required. The maximum allowed current on the GSC400 AC current terminals is 5A. U Use large AWG wires for runs longer than 5ft. The shunt resistors used for sensing of current are very low resistance. The accuracy can be affected by resistance of CT wires.
Figure 7 – CT Installation Do’s and Don’ts (from DWG1469R1.0) 2.9 AC Current and Voltage Calibration Each GSC400 undergoes an advanced two point calibration at the factory and typically does not required calibration except in the following instances: 1. Current Transformers (CT) are used that have poor tolerances. 2. The AC signal from the generator is distorted with a high total harmonic distortion (THD). One cause is VFD (Variable Frequency Drive) devices.
2.10 Configurable Switched Inputs / Configurable Outputs 1 2 Configurable Switched Inputs Configurable Outputs Menu Location Advanced Setup > Inputs Setup Advanced Setup > Outputs Setup Page 67 69 Configurable Switched Inputs Four of the switched inputs (A to D) trigger when battery + is applied. The other four inputs (E to H) trigger when battery - is applied. The switch inputs are user programmable. They are disabled by default.
Figure 8 – Configurable Switched Input / Configurable Output Example
of 148 2.10.1 Timed Output on Failure Shutdown If you wish to provide a timed output when the engine shuts down you can do the following. 1. Set the “Energized to Stop” feature to one of the Switched Inputs A to H. 2. Set the “Energized to Stop” duration in the Engine Logic menu to the duration you wish to time the configurable output. 3. Set the desired Configurable Output you wish to have timed. Only failures are valid. Wire the GSC400 as shown below.
of 148 2.
of 148 Troubleshooting Notes 1. To check for proper CAN communications place GSC400 in AUTO mode with the ECU powered and check that the engine temperature on the front panel display is not displaying N/A (engine temperature must be set to J1939). “N/A” indicates no communications with the ECM. 2. The ECM should start and run the engine – even if there are no CAN communications with the GSC400 – when the GSC400 turns on the fuel and crank outputs.
of 148 2.12 Modbus Setup 1 Modbus (RS485) Menu Location Advanced Setup > Set Modbus Page 74 Modbus has the capability to start and stop the genset and to transition from OFF to AUTO to do this. Modbus should be disabled while performing maintenance or repairs by unplugging the Modbus connector. GSC400 has a RS485 connection and supports the Modbus protocol. It is a slave device and must be polled by a master.
of 148 Communication Notes: 1. The GSC400 only supports commands 0x03 (read multiple registers) and 0x06 (write single register). If an attempt is made to send another command the GSC400 returns “incorrect command”. 2. Can only request to read 20 registers at a time. If over 20 GSC400 returns “illegal data address”. 3. Also need to watch out for discontinuities in register map. The GSC400 will return invalid data for non-existing registers (often returns a value of 0). 4.
of 148 2.13 Idle Mode 1 2 Configurable Switched Inputs Configurable Outputs Menu Location Advanced Setup > Inputs Setup Advanced Setup > Outputs Setup Page 67 69 For generators that have the capability of idling at a lower speed than the speed at which power is produced, the GSC400 controller has an Idle Mode feature that suppresses the warnings and failures for under-voltage, under-frequency, and under-speed. The GSC400 displays “Idle Running” when this feature is enabled.
of 148 Figure 10 – Idle Mode during warm-up and cool-down application note.
of 148 This page intentionally left blank.
of 148 3. GSC400 Configuration This section will explain the various menus used to configure the GSC400. Most GSC400 configuration is done from the Advanced Setup Menu. 3.1 MAKING MENU SELECTIONS ......................................................................................................44 3.2 ADVANCED SETUP MENU OVERVIEW ........................................................................................45 3.3 ENGINE LOGIC ..................................................................
of 148 Important! For Firmware Versions Below 2.00 After changing any settings on the controller, the controller needs to be reset. This can be done one of two ways: 1. Power off, wait for 2s, and power on the controller. 2. Press the Run key, wait until the controller begins the start sequence and then press the OFF key. You will see a flickering of the screen as the controller updates. The GSC400 incorporates an Advanced Setup menu. Only OEMs or knowledgeable users should change these parameters.
of 148 If you are satisfied with the selection then you must highlight the selection and then press enter. You will then be taken back to the previous menu. If there is no checkmark you must make a selection. See the next bullet point. If you wish to make another selection scroll down to the desired selection and press enter. A checkmark should appear beside the option selected. Then – with the desired option still selected – press enter again to exit the menu. 3.
of 148 Exerciser Set Inputs Setup (i.e. Configurable Switched Inputs) Battery Setup Set Password Set Maintain Set Modbus Common Faults Other Settings occurs. Generators require periodic operation as part of their scheduled maintenance. This menu allows settings to control how often the engine/generator is started and for how long. This menu allows you to assign features/warnings, for example low oil pressure, to one of eight digital inputs.
of 148 3.3 Engine Logic The Engine Logic menu contains settings that control the starting and stopping of the engine. All parameters in bold below are located in the engine logic menu unless otherwise noted. The Crank Disconnect setting determines the speed that must be attained before the crank output is turned off and the genset is considered to be running. The Crank Oil Pressure parameter is used to determine when to check for the Locked Rotor condition.
of 148 If the Midheat Time is greater than zero, the glow plug output remains on during cranking but not during crank rest. The glow plug output turns off if a crank failure occurs, once crank success is reached (unless the PostHeat is set to a value greater than 0s), or if the Midheat time expires. After the crank rest delay expires, the controller turns on the fuel and crank outputs and attempts to start the generator again. This is repeated until the number of tries equals the Crank Attempts.
of 148 go into Cool Down mode where an output is turned on (one of the configurable outputs must be set to Cool Down). Once the Cool Down time has expired, the fuel relay is turned off and the controller enters the OFF mode. By default it is possible to manually bypass cool down by pressing the OFF or AUTO keys. To prevent this, the Bypass Cooldwn can be set to disabled. If a failure occurs, cool down is bypassed and the GSC400 goes into the FAILURE mode.
of 148 3.4 Sensor Inputs The GSC400 has support for the following sensor types: Table 7 – GSC400 Engine Parameters Engine Parameter Advanced Menu Location High Engine Temperature High Engine Tmp Oil Pressure Oil Pressure Fuel Level Fuel Level Oil Level Oil Level Fuel In Basin Fuel In Basin Low Engine Temperature Low Engine Tmp Auxiliary Analog 1 Aux Analog 1 Auxiliary Analog 2 Aux Analog 2 Negative engine temperatures are not allowed for the sender inputs on the GSC400.
of 148 triggered. The controller will display a message and sound the alarm in the case of a warning or will shut down and sound the alarm in the case of a failure. 3.4.1 Switched Inputs If using a switch, it must be switched to ground but can be either normally open or normally closed. Set the “ Signal Source ” menu to “Switch Input” and the “ Switch Setting ” menu to “Closed = Fail” for normally open switches or “Open = Fail” for normally closed switches.
of 148 3.4.2 Senders Table 8 – Default Sender Tables Signal Source Front Panel Menu Name High Engine Temperature / Low Engine Temperature Oil Pressure Sender Part Number** Supported Sender Input Pins* Front Panel Menu Name Sender Part Number**, *** Supported Analog Input Pins* Sender 1 Sender 2 Sender 3 Datcon 1 Dat Pin2 VDO 2 Datcon DAH (e.g. 2022-00, 02024-00, and 02025-00) Datcon DAH (e.g.
of 148 Open Sender Detection or Shorted Sender Detection provides diagnostics on the sender. See the installation chapter for more details. Set to Warning, Failure, or Disable. When changing the units, the controller will do a conversion of all settings to the new unit. It is possible that the conversion will cause one or more settings to go out of bounds. 3.4.4 Low and High Engine Temperature The Low and High Engine Temperature types can share the same sender.
of 148 They can be programmed with low and high warning and failure levels. The warnings and failures are displayed as “Short Aux An1”, “Open Aux An1”, “Low Aux An1”, and “High Aux An1”. The “Aux An1” is the programmable portion mentioned above. They can be programmed to measure and display three measurement types: Temperature, Pressure, and Level. These special submenus are located under the standard submenu items in the Aux Analog 1 / 2 menus.
of 148 3.5 Speed Sensing The speed sensing menu allows you to select the source to use for sensing the rotational speed of the engine. There are three options to choose from: 1. J1939 Input – If the engine/generator comes equipped with an engine control module (ECM) that supports the J1939 protocol then the GSC400 can obtain the engine speed from the ECM. 2.
of 148 For example if you have 100 teeth on the flywheel that the magnetic pickup sensor is attached to and the speed that your generator runs to produce power is 1800RPM the calculation would be: Rated Frequency (Hz) = (100 x 1800) / 60 = 3000Hz. You would enter 3000Hz for the Rated Frequency. Refer to the following tables for more examples.
of 148 3.6 Battery Setup The Battery menu allows the user to set the low and high battery warning and failure levels. In addition, the generator can be made to automatically start when in the AUTO mode if the voltage drops below the Recharge Level. The controller will display Low Voltage During Cranking on the screen if during cranking the voltage drops below the Low Vol InCrank setting. Note: When the generator is running, the battery voltage will equal the alternator charging voltage.
of 148 3.7 Generator (AC Voltage / Current / Frequency) Setup The AC Frequency, AC Voltage, and AC Current menus allow the measurement and display of the AC voltage, current, and frequency from the generator. 3.7.1 AC Frequency In the AC Frequency menu, under and over frequency warnings and failures can be configured. The DisconnectFreq setting is used by the GSC400 controller as a backup to the speed input (only if speed is set to magnetic pickup).
of 148 Selecting a Voltage Group to Use The Voltage Group submenu can be used for this purpose. Alternatively one or two configurable switched inputs can be used to determine the voltage group to be used. See section 3.7.2.1 below. The configurable switched inputs override the Voltage Group submenu. Table 12 – GenSet Configurations and How to Configure Them in the GSC400 Refer to Figure 5 on page 29 for a diagram of each of the various three phase configurations.
of 148 Table 13 – AC Voltage Submenus that apply to Voltage Groups Voltage Groups Voltage Group 1 Voltage Group 2 Voltage Group 3 Voltage Group 4 Submenus that apply for the Voltage Group Group 1 Setting Over Volt Warn 1 Over Volt Fail 1 UnderVoltWarn1 Under VoltFail1 Over Volt Warn 2 Over Volt Fail 2 UnderVoltWarn2 Under VoltFail2 Group 3 Setting Over Volt Warn 3 Over Volt Fail 3 UnderVoltWarn3 Under VoltFail3 Group 4 Setting Over Volt Warn 4 Over Volt Fail 4 UnderVoltWarn4 UnderVoltFail4 Descript
of 148 3.7.2.1 Voltage Select Inputs You can choose a voltage configuration by setting one or two of the configurable switched inputs to Volt Select 1 and Volt Select 2. This allows the GSC400 to automatically re-configure its voltage display as well as warning/shutdown trip points relating to AC voltages and currents. This is useful for mobile generators where the voltage selections can be selected via a CAM switch. Warning: The Voltage Select Inputs override the Voltage Group parameter.
of 148 3.7.3 AC Current The GSC400 controller is designed to measure AC current from the generator with the use of current transformers (CTs). The maximum current on the AC current terminals of the GSC400 is limited to 5A. The “Turns Ratio” sub menu is used to setup the CT ratio. All numbers in this menu are in terms of 5A. For example selecting 1000 is the same as 1000:5A (the GSC400 displays 1000A on the screen when the current measured on the GSC400 AC Current terminals is 5A).
of 148 3.8 J1939 Setup The GSC400 will work with any generator as long as it supports the standard messages listed in the SAE J1939 specification. Standard messages include oil pressure, engine temperature, and engine speed. Some engine control modules have proprietary messages that are intended for specialized devices and are not displayed by the GSC400. Viewing Engine Parameters from J1939 To use J1939 instead of a local switch or sender: 1.
of 148 Table 16 – J1939 Addition Parameter Display Options. Engine Manufacturer Display Group 1 Display Group 2 John Deere Engine Torque (%) Friction Torque (%) Load (%) Intake Temperature ( 0 C) Fuel Temperature ( 0 C) Fuel Rate (L/min) Engine Torque (%) Friction Torque (%) Load (%) Set Speed (RPM) ECM Battery (V) Load (%) Fuel Rate (L/min.) Set Speed (RPM) ECM Battery (V) Load (%) Fuel Rate (L/min.
of 148 until the GSC400 accesses the data from the bus. Note that loss of ECM may not be triggered since other parameters may be receiving data from the bus. ECM Boot-up Delay ECMs can take up to 10s to boot-up when they are first powered. Ensure that the crank time is long enough to take this into account. If extended cranking is not desired the glow plug (preheat) time can be set to turn on the fuel relay for a set time before cranking begins. Ensure that no configurable output is set to preheat.
of 148 The user can enable/disable the DTC feature and configure its behavior with the following settings. DTC DISPLAY – This setting enables or disables active fault messages (DM1) monitoring. When the DTC DISPLAY feature is enabled the GSC400 can receive active faults in the RUNNING, OFF and AUTO modes on the J1939 bus. Any new received active faults will trigger a message "NEW ACTIVE DTC" and the user can read the message on the GSC400 front panel display.
of 148 3.9 Digital Inputs (Configurable Switched Inputs) Setup There are eight configurable switched inputs. Each input can be selected to any of the features given in Table 18 below. Table 17 – Configurable Switched Input Selections Name Low Air Pressure Low Hydraulic Pressure Low Oil Pressure EPS Supplying Load Description This input generates a Low Air Pressure failure when active only in Crank. It is ignored in the OFF, AUTO, and RUN modes.
of 148 Running” is displayed on the GSC400 display when this input is active. The idle mode can also turn on a configurable output (see the Voltage Regulator configurable output feature in Table 18 on page 69). This output is usually used to turn off the generator voltage regulator when idle mode is entered but can be used for any purpose.
of 148 3.10 Digital Outputs (Configurable Outputs) Setup There are eight 200mA configurable outputs (all switched to ground) and one 40A digital output (dry contact), the Extra Relay output, all of which are configurable. Each feature (listed in Table 18 below) is permitted to be set to only one configurable output.
of 148 Over RPM Warning [Over Speed Warning] Low Fuel Failure Low Fuel Warning Battery Failure Battery Warning Low Coolant [Level] Failure Low Coolant [Level] Warning Not In Auto General Failure Crank Rest Engine Running Engine Cranking Exerciser Alarm Battery Recharge Alarm Under Voltage Warning Over Voltage Warning Over Current Warning Fuel In Basin Warning Voltage Regulator Low Temperature This turns on the digital output if the Over Speed Warning is activated. See section 3.5 for more details.
of 148 Warning Backlight Auxiliary Warning Temperature Warning (section 3.4) is activated. This turns off the digital output if the LCD backlighting turns off. The controller enters the sleep mode (section 4.4.2) when this occurs. This turns on the output if the Auxiliary Warning Digital Input (see Table 17 in section 3.9) is active. Maintenance Timer This turns on the output if maintenance is required to be performed on the engine/generator. See section 3.13.
of 148 3.11 Exerciser Setup The GSC400 can be set to automatically start the genset at regular intervals while in the AUTO mode. This is controlled by the Exerciser Setup menu. The Exerciser Enable should be set to Enabled if this feature is desired. The GSC400 will display a message and sound the buzzer for a set amount of time (Pre-Alarm Delay) to alert nearby personnel that the generator is about to start. The engine/generator will run for a set period of time (Run Duration) and then shut down.
of 148 3.12 Password Setup The GSC400 allows a 4 digit password to be entered to protect the advanced setup menu from any unauthorized changes. This password will be needed to perform any changes to the advanced setup. If the password is entered incorrectly, the controller will allow 3 more tries before the GSC400 returns back to the main menu. To set each digit of the password, do the following: Select Password No.1 (Digit 1) Enter the desired number 0-9 Select Password No.
of 148 3.13 Set Maintain This menu controls the service feature that is used to alert the user of required generator maintenance and can be enabled or disabled from this menu. If enabled, the count interval menu allows the user to set the number of hours until next service. The number of hours to next service is displayed in the Basic Setup menu under Maintenance (see Table 6 on page 90).
of 148 Figure 11 – Example of Common Fault 1 Usage 3.16 Other Setting The Other Setting menu contains the settings used to control the features in the following sections. 3.16.1 Dummy Load The dummy load feature allows the user to turn on an output if the AC current is below a settable threshold (Load On Point). This is useful for applications where the generator must have a minimal load to prevent damage to the generator.
of 148 3.16.2 LCD Heater There is an option for an LCD heater that allows the LCD display to operate normally down to -400C (for more information contact Dynagen). There is an option in the “Other Setting” menu called “LCD Heater” that allows the heater to be enabled or disabled. It is set to disabled by default. 3.16.3 Fan Control The fan control is meant to operate in conjunction with the engine run configurable output. The fan control also has a “fan control” configurable output that must be set.
of 148 Table 19 – Fan Control GSC400 Mode Before RUN (Crank Success) After RUN (Crank Success) After RUN (Crank Success) AND engine temperature above setpoint.
of 148 4. Operation and End-User Configuration This section will explain how to operate the GSC400 and the settings the end user can change (such as the time and date). 4.1 4.2 4.2.1 4.3 4.4 4.4.1 4.4.2 4.4.3 4.4.4 RECOMMENDED MAINTENANCE .................................................................................................79 POWER-UP..................................................................................................................................79 Controller Alarming .......
of 148 4.1 Recommended Maintenance The actions in Table 20 should be performed routinely. WARNING: When performing any maintenance on the GSC400 ensure that the controller is in the OFF mode, is isolated from all possible sources of power and the crank wire is removed from the controller. U U Table 20 – Recommended Maintenance Procedure Making the controller safe for inspection and maintenance.
of 148 3. Press the DOWN key until “Basic Setup” is highlighted and press the enter key. 4. Press the down key to select “Contrast Adj.” and press enter. 5. Use the up and down keys to adjust the contrast and then press enter. 6. Then scroll up to select “Back” and press enter. Repeat this again to exit the menu system and go back to the OFF mode. The controller will then enter the OFF mode. By default, it is possible to manually start the generator in the OFF Mode.
of 148 the GSC400 will sound an audible alarm and display “Emergency Stop” on the LCD display. See Figure 4 on page 17 for the location of the emergency stop input.
of 148 4.4 Controller States The GSC400 incorporates 3 primary modes of operation: 1. OFF Mode 2. AUTO Mode 3. RUN Mode 4.4.1 OFF Mode When the GSC400 is set to the OFF mode, automatic starting will be disabled. No automatic controls will be initiated. The OFF mode may be initiated when no generator controls are required or when the controller configuration requires adjustment. The user can disable manual start in OFF mode in the basic menu. See section 4.8.2.
of 148 4.4.3 AUTO Mode When the GSC400 is set to the AUTO mode, automatic starting will be enabled. Possible triggers include RSC (start/stop), battery recharge and exerciser run (all of which are controllable from the menu system). If the engine is started, failures will be automatically detected allowing for safe engine operation. While in AUTO mode the controller will display engine temperature, battery voltage, fuel level, and engine hours. The LCD will turn off after a programmable amount of time.
of 148 the switched input connector. The controller will automatically shut the GenSet down and re-enter the AUTO mode if it initiated a generator start. When the controller is in the RUN mode, generator parameters will be displayed on the screen to allow the user to monitor the engine status. These include engine speed, generator voltage and current, and engine temperature as well as others. The parameters are displayed in groups and the screen scrolls between the various groups.
of 148 4.5 GSC400 Start / Stop Behavior THE LCD WILL TURN OFF DURING THE FIRST 2 SECONDS OF CRANKING TO LIMIT THE VOLTAGE DIP EFFECT ON THE CONTROLLER DURING CRANKING. Since the GSC400 startup and shutdown behavior can be configured by the manufacturer the exact startup and shutdown behavior can vary. Behaviors such as the amount of time to wait before starting, preheat, crank time, etc, all are programmable. There are three ways to start the generator (start conditions): 1.
of 148 Off key pressed during Manual Run If the Off key is pressed during a manual Run, a cool down popup will display on the GSC400. Press the AUTO key to immediately enter the Auto mode, press the OFF key to immediately enter the OFF mode, or press the Enter key to enter cool down. If no key is pressed the GSC400 will remain in the Run mode. If the OFF key is pressed during another start condition (e.g.
of 148 4.7 GSC400 Menu System Operation The GSC400 incorporates a menu system to allow the end user to adjust basic settings. The menu system also allows technicians and OEMs to adjust advanced settings (this feature is password protected). With the controller in the OFF Mode, the menu system may be selected simply by pressing the Enter key. In the OFF Mode press “ENTER” to access the GSC400 Menu System. This is called the Basic Menu. The following keys perform the menu navigation: 1.
of 148 Table 21 - Basic Menu Layout Clock Setup Basic Menu Basic Setup Events History Year Month Date Day Hour Minute 12/24 Contrast Adj.
of 148 4.8.1 Clock Setup The Clock Setup menu will allow you to set the clock. The clock is important if you are planning to use the event log (records all failures and warnings and when they occurred) or the exerciser feature (starts the generator for a settable period).
of 148 The controller can be made to NOT sound the alarm when the controller is not in the AUTO mode. This is controlled by the Not In Auto setting. “Disable Beep” is the default selection. The OFF Mode Start setting can be set to Enable to allow a manual start from the OFF mode. Otherwise a manual run can only be performed when the controller is in the AUTO mode.
of 148 4.8.3 Event History Log The GSC400 incorporates an event history logging system. When engine failures, events, or DTCs (Diagnostic Trouble Codes) occur, an entry is created in the GSC400 Event History Log. See Table 24 – – Event Log Entries below for the possible events that are stored. A total of 100 entries can be recorded. Entries may be viewed simply by scrolling up or down using the “UP” and “DOWN” keys.
of 148 Table 24 – Event Log Entries A “*” beside the Event Entry indicates the Event is a GSC400 event. All other events are failures (see page section 4.10 on page 98). Event Entry Description ADC SWITCH FAILURE These are internal GSC400 failures. Try power cycle the GSC400. If the failure occurs ADE READ FAILURE repeatedly the unit could be defected. ADE WRITE FAIL AUTO ENABLE* Auto button on front face of controller pressed. GSC400 placed in AUTO mode.
of 148 INITIALIZING* KEY BOARD FAILURE LOCKED ROTOR LOG CORRUPTED LOSS OF ECM COMM LOW AIR PRESSURE LOW AUX AN1 LOW AUX AN2 LOW BATTERY LOW COOLANT [Level] LOW FUEL LEVEL LOW HYDRAULIC LOW OIL LEVEL LOW OIL PRESSURE MAINTENANCE NEEDED* MAINTENANCE PERFORMED* MANUAL START* MANUAL STOP* OFF ENABLE* OPEN AUX ANALOG 1 EEPROM is being loaded with factory defaults. This occurs on first power up or if the user resets the GSC400 to factory defaults from the PC Configurator.
of 148 OPEN AUX ANALOG 2 OPEN ENG TEMP OPEN ENGINE TEMP OPEN FUEL BASIN OPEN FUEL LEVEL OPEN OIL LEVEL OPEN OIL PRES OVER CRANK OVER CURRENT OVER FREQUENCY OVER SPEED OVER VOLTAGE POWER ON* RECOVERY REMOTE START* REMOTE STOP* RS232 FAILURE RS485 FAILURE SHORT AUX ANALOG 1 SHORT AUX ANALOG 2 SHORT ENG TEMP SHORT ENGINE TEMP SHORT FUEL BASIN SHORT FUEL LEVEL SHORT OIL LEVEL SHORT OIL PRES TLE6230 FAILURE UNDER FREQUENCY UNDER SPEED UNDER VOLTAGE voltage.
of 148 4.9 GSC400 LED Status Indicators Some industry standard failures, warnings, and events on the GSC400 are indicated by a series of LEDs on the left side of the controller. Specific LED indicators will be illuminated depending upon the condition of the controller. The GSC400 LED indicators allow a quick check of the controller’s condition. The GSC400 displays multi color LED’s for specific condition representation.
of 148 Table 25 – GSC400 Lamp Indication Meanings LED Description Over Crank High Eng Temp LED Color Solid Red A solid red illuminated LED represents an Over Crank condition on the final crank attempt. This is a Failure. Yellow Solid Yellow A solid yellow illuminated LED represents an Over Crank Warning condition when there are crank attempts still remaining. Red Solid Red A solid red illuminated LED represents a High engine Temp Failure condition.
of 148 LED Description Not In Auto Low Coolant LED Color Red Red LED Status Solid Red Indication A solid red illuminated LED represents a Not in Auto condition. Flashing Red A flashing red illuminated LED means the GSC400 is in OFF – sleep mode. Solid Red A solid red illuminated LED represents a Low Coolant (Temperature and/or Level) failure condition.
of 148 4.10 Warnings and Failures The GSC400 incorporates many types of warnings and failures. Most are only active in the RUN mode while a few are also active in the AUTO and/or OFF modes. Warnings and failures can be triggered from a Switched Input, Analog Input, AC Voltage, AC Current, Speed Signal Input, as well as others. The Advanced Setup section of this manual will give more information of the specific warning and failures for each type of input.
of 148 4.10.1 Returning to OFF Mode from a Failure When the GSC400 enters in the FAILURE mode press the Off key. This will silence the alarm and “ENTER TO RESET?” will appear on the GSC400 display. Press the Enter key to exit the FAILURE mode and enter the OFF mode. Note: it is not possible to enter the AUTO mode directly from the FAILURE mode. 4.10.2 Diagnostic Trouble Code Shutdowns This section only applies for electronic engines and if the Diagnostic Trouble Code (DTC) feature is enabled.
of 148 For mechanically-connected engines, once the maximum is reached it will continue to display the maximum unless the hourmeter is reset through an authorized dealer. J1939 has the priority; it overrides the local engine hour value when the GSC400 is connected to J1939. 4.11 J1939 This section applies if J1939 is enabled for one or more parameters. The parameters are displayed the same for J1939 as they are for analog inputs.
of 148 4.12 J1939 Diagnostic Trouble Code (DTC) Display This section applies for electronic generators (i.e. generators that use J1939) which have the DTC feature enabled. The GSC400 can read J1939 diagnostic trouble codes (DTCs) from an electronic ECM, if enabled (see section 4.1.3 on page 65 for information on how to configure and customize the GSC400 DTC feature). 4.12.1 DM1 Messages When the engine’s ECM detects a fault, it will send an Active Diagnostic Trouble Code, DM1, message.
of 148 Figure 13 – Single Active DTC message Figure 14 – Five active DTC messages and the 3PrdP one being displayed The user can also manually cycle through the DTC messages by activating either the "UP" or "DOWN" key after the screen has been locked. If the user stops at a specific DTC message the display screen will remain on that message for a period of 10 seconds before it begins scrolling again.
of 148 stored message at a 3 second interval. If the user intervenes, the interval will change to 10s. The DTC stored message display appears as follows: Figure 15 – 32 stored DTC messages, the 5PthP stored code being displayed To Trigger a DM2 Request, simultaneously press the "UP" and "DOWN" keys for a period of 3 seconds in either the AUTO, OFF, or RUNNING modes. The controller’s alarm will sound and the controller will send a request to the ECM.
of 148 This page intentionally left blank.
of 148 Appendix A GSC400 Detailed Advanced Menu Layout Table 26 – Submenus of the Advanced Menu Main Menu J1939 Setup Sub Menu Manufacturer Loss of ECM Display Group 1 Display Group 2 DTC Display Active DTC Log Read Stored DTC Auto Power ECM ECM Power Delay Cummins Idle High Engine Tmp Oil Pressure Fuel Level SPN Conversion EMS2B Freq Sel EMS2B Acc Pedal Input Pin Signal Source Bypass Delay Switch Setting Shorted Sender Open Sender Units Warning Level Failure Level Input Pin Signal Source Bypass
of 148 Oil Level Fuel In Basin Low Engine Tmp Aux Analog 1 Open Sender Units Warning Level Failure Level 0% Fuel Level 25% Fuel Level 50% Fuel Level 75% Fuel Level 100% Fuel Level Input Pin Signal Source Bypass Delay Switch Setting Shorted Sender Open Sender Units Warning Level Failure Level Input Pin Signal Source Bypass Delay Switch Setting Shorted Sender Open Sender Units Warning Level Failure Level Input Pin Signal Source Bypass Delay Switch Setting Shorted Sender Open Sender Units Warning Leve
of 148 Aux Analog 2 Speed Sensing AC Frequency A/C Voltage Pres Low Fail Level Units Level High Warn Level High Fail Level Low Warn Level Low Fail Analog Group Input Pin Signal Source Bypass Delay Switch Setting Shorted Sender Open Sender Temp Units Temp High Warn Temp High Fail Temp Low Warn Temp Low Fail Pres Units Pres High Warn Pres High Fail Pres Low Warn Pres Low Fail Level Units Level High Warn Level High Fail Level Low Warn Level Low Fail Analog Group Signal Source Rated Freq Rated RPM Over
of 148 A/C Current Engine Logic Under Volt Warn 1 Under Volt Fail 1 Over Volt Warn 2 Over Volt Fail 2 Under Volt Warn 2 Under Volt Fail 2 Over Volt Warn 3 Over Volt Fail 3 Under Volt Warn 3 Under Volt Fail 3 Over Volt Warn 4 Over Volt Fail 4 Under Volt Warn 4 Under Volt Fail 4 Current source Turns Ratio Over Current Warn 1 Over Current Fail 1 Over Current Warn 2 Over Current Fail 2 Over Current Warn 3 Over Current Fail 3 Over Current Warn 4 Over Current Fail 4 Hi Wye Current Cur Warn Latch Delay to S
of 148 Digital Output Setup All selections apply to each individual output Exerciser setup Digital Input Setup Battery Setup Extra Relay Output A Output B Output C Output D Output E Output F Output G Output H Disable, Warm-Up, ETS, Glowplug, Cooldown, Over Crank , High Temp Fail , High Temp warn, Low Oil Fail , Low Oil Warning, Under RPM Fail, Under RPM Warn, Over RPM Fail Over RPM Warn, Low Fuel Fail Low Fuel Warn, Battery Fail, Battery Warn, Low Coolant Fail, Low Coolant warn, Not in Auto, Failu
of 148 Set Password (Four Digits Long) Set Maintain Set Modbus Common Faults Other Setting Password No. 1 (Digit 1) Password No. 2 (Digit 2) Password No. 3 (Digit 3) Password No.
of 148 Appendix B Default Configuration Settings GSC400’s are factory programmed and shipped with default settings loaded into the controller. These are the defaults of the settings located in the Advanced Setup Menu.
of 148 Oil Level Fuel In Basin Low Engine Temperature Aux Analog 1 Input Pin Signal Source Bypass Delay Switch Setting Shorted Sender Open Sender Units Warning Level Failure Level Input Pin Signal Source Bypass Delay Switch Setting Shorted Sender Open Sender Units Warning Level Failure Level Input Pin Signal Source Bypass Delay Switch Setting Shorted Sender Open Sender Units Warning Level Input Pin Signal Source Bypass Delay Switch Setting Shorted Sender Open Sender Temp Units Temp High Warn Temp H
of 148 Aux Analog 2 Speed Sensing AC Frequency AC Voltage Input Pin Signal Source Bypass Delay Switch Setting Shorted Sender Open Sender Temp Units Temp High Warn Temp High Fail Temp Low Warn Temp Low Fail Pres Units Pres High Warn Pres High Fail Press Low Warn Press Low Fail Level Units Level High Warn Level High Fail Level Low Warn Level Low Fail Analog Group Signal Source Rated Freq Rated RPM Over Speed Warn Over Speed Fail Under Speed Warn Under Speed Fail Frequency Disconnect Over Freq Warn Ove
of 148 AC Current Engine Logic Digital Output Setup All selections apply to each individual output Exerciser setup Over Volt Warn 3 Over Volt Fail 3 Under Volt Warn 3 Under Volt Fail 3 Over Volt Warn 4 Over Volt Fail 4 Under Volt Warn 4 Under Volt Fail 4 Current source Turns Ratio Over Current Warn 1 Over Current Fail 1 Over Current Warn 2 Over Current Fail 2 Over Current Warn 3 Over Current Fail 3 Over Current Warn 4 Over Current Fail 4 Delay to Start Pre-heat Time Crank Time MidHeat Time Crank Re
of 148 Digital Input Setup All selections apply to each individual input Battery Setup Set Password Set Maintain Set Modbus Common Faults Other Setting Input A (Bat) Input B (Bat) Input C (Bat) Input D (Bat) Input E (Gnd) Input F (Gnd) Input G (Gnd) Input H (Gnd) Low Auto Charge Charge Pre-Alarm Charge Duration Recharge Level Low Warn Level Low Fail Level High Warn Level High Fail Level Low Vot InCrank Password No. 1 Password No. 2 Password No. 3 Password No.
of 148 Appendix C GSC400 Fixed Warning/Failure/Event Delays The below table lists the fixed delays of the GSC400.
of 148 Oil Pressure Warning Fuel Level Failure Fuel Level Failure (switch setting) Fuel Level Warning Fuel Level Warning (switch setting) Oil Level Failure Oil Level Failure (switch setting) Oil Level Warning Fuel In Basin Warning Fuel In Basin Warning (switch setting) Low Engine Temperature Warning Low Engine Temperature Warning (switch setting) Auxiliary Input 1 and 2 Warning Auxiliary Input 1 and 2 Failure 5s 6s 4s 5s 4s 6s 4.75s 5s 5s 5s 5s 5.
of 148 Under Voltage Failure AC Voltage Phase B Under Voltage Warning AC Voltage Phase B Over Voltage Failure AC Voltage Phase B Over Voltage Warning AC Current Phase B Over Current Failure AC Current Phase B Over Current Warning EPS Supplying Load (>5%) Phase B AC Voltage Phase C Under Voltage Failure AC Voltage Phase C Under Voltage Warning AC Voltage Phase C Over Voltage Failure AC Voltage Phase C Over Voltage Warning AC Current Phase C Over Current Failure AC Current Phase C Over Current Warning EPS
of 148 Cranking Oil Pressure Low (Locked Rotor) Low battery during cranking LCD indication High Battery Level Failure High Battery Level Warning Low Battery Level Failure Low Battery Level Warning Low Battery Level Recharge ECM Loss of Communication detected. 2s Battery 0.5s 12s 7.5s 4s 5.5s 10s J1939 5.
of 148 Appendix D Accessory List D.
of 148 D.3 CT’s (Current Transformers) Table 31 – Current Transformers Part List CT Description 100A:5A 200A:5A 300A:5A 500A:5A 600A:5A 1000A:5A 1500A:5A Stock Code ACC0045 ACC0046 ACC0047 ACC0048 ACC0049 ACC0050 ACC0057 Manufacturer’s Part No. PC&S-546-100-L PC&S-546-200-L PC&S-546-300-L PC&S-546-500-L PC&S-546-600-L PC&S-546-1000-L PC&S-546-1500-L D.4 Senders Senders are required if display of engine parameters, warnings and failures are required.
of 148 Table 33 – Relay Part List Relay Description Stock Code Manufacturer’s Part No. 12VDC AZETTLER RLY0029 AZ-973-1C-12DC 24VDC AZETTLER RLY0043 AZ-973-1C-24DC 12VDC HASCO RLY0053 CAR-1A-40-DC12S 24VDC HASCO RLY0054 CAR-1A-40-DC24S D.6 GSC400 Fusing Output relays are protected by onboard 40A fuse protection. Smaller amperage fuses from many automotive stores may be used in place of the higher current 40A.
of 148 Appendix E Modbus Map The GSC400 follows the Modbus standard. Modbus is a master-slave communication protocol in which only the master can initiate a communication request. A slave device never initiates communications. Please refer to the standard for more details. E.1 Communication Details The GSC400 communicates on Modbus only as a slave device. The GSC400 supports only the modbus RTU (Remote Terminal Unit) mode. Query and response messages share the same message structure.
of 148 modbus register 40002. Use “0x01, 0x2C” for modbus register 40300. 2. The third and forth bytes specifies the number of registers to read. Larger requests will generator a modbus error. For example use ‘0x00, 0x14” to read 20 registers. 0x06 – Write Single Register Note: There are only two addresses that support the 0x06 command: 40098 and 40130. The Data field contains 4 bytes: 1. The first two bytes specifies the starting register to write to (value = modbus register - 40000). 2.
of 148 When the GSC400 controller goes from the Run to OFF or Menu to OFF, modbus communications will be unavailable until the controller is in the OFF mode for 2 seconds.
of 148 E.2 Register Map NOTE: All parameters are assumed to be unsigned integer values unless otherwise specified in the “Range” column. U Table 35 – Modbus Register Map Register Parameter Range Read / Write Data format Units 1 st Generation ModBus Support P P (For new applications utilize 2 nd generation support) P P Warning and fault shutdown are updated by controller once every 250ms.
of 148 40007 40008 40009 40010 Events number 13 Generator Not In Auto Mode bit 4-0 Events number 14 Battery Charger Fault bit 9-5 Events number 15 Battery Voltage Low bit 14-10 Events number 16 Battery Voltage High bit 4-0 Events number 17 Low Battery Voltage During Cranking bit 9-5 Events number 18 Locked Rotor bit 14-10 Events number 19 Common Fault #1 Warning/Shutdown bit 4-0 Events number 20 Common Fault #2 Warning/Shutdown bit 9-5 Events number 21 Reserved bit 14-10 Reserved
of 148 40081 bit0: EPS supplying load shutdown (red) bit1: EPS supplying load (green) bit2: not used bit3 : Glow plug on (green) bit4 : Failure is active (Red Failure LED) bit5 to bit7: (not used) bit8: Crank relay On (no LED) bit9: Fuel relay ON (no LED) bit10: Extra relay ON (no LED) bit11 to bit13: (Reserved) bit14 and bit 15: (not used) 40082 Events / Warnings Status 0 = OFF, 1 = ON R bit0 : Warm up finished bit1 : ETS is on bit2 : Glow plug is on bit3 : Cool Down is active bit4 : Over crank o
of 148 bit will flash) bit9: Battery charging pre-alarm is active (this bit will flash) bit10: AC under voltage warning bit11: AC over voltage warning bit12: AC over current warning bit13: Fuel in basin warning bit14: Voltage Regulator Digital Output feature is on.
of 148 bit8: Auxiliary input failure bit9: Low battery level failure bit10: High battery level failure bit11: AC over voltage failure bit12: AC under voltage failure bit13: AC over current failure bit14: J1939 Loss of ECM failure bit15: EPS load failure 40086 bit0: PGN 61444 EEC1 not available (engine speed) (f/w bit1: versions PGN 65263 Fluid level not available (oil pressure) 2.
of 148 40095 LSB = NOT USED 2. START/STOP CONTROL AND COMMAND Start/Stop registers are polled by the controller every 250mS. 40098 SYSTEM DISABLE 0x5DA2 W When 0x5DA2 is written to address 40098 this places the controller in the (23970) OFF mode (System disabled). The register is read in all controller operating modes (Running, Auto, Failure, Menu/sleep modes). CAUTION – when received in the Running mode the controller immediately goes to the OFF mode (no cool-down is performed).
of 148 REQUEST DM2 0xBB44 W Send a request to controller for reading the previous DTC codes. If the controller read the previous DTC code success, the data will be updated in the range of 40180 to 40244. This registers can hold maximum 32 DTC code 3. SYSTEM CONTROL STATUS Read Only. Allows user to determine current controller mode (and sub-mode). Any active events or warnings will be displayed up to a maximum of 6.
of 148 36 EXERCISER RUNNING 0 None of the above. 0 corresponds to none of the above sub modes of operation. 40102 Active Event ~ message queue 40107 0 ~ 255 R (Read Only) A maximum of 6 events/warnings are stored concurrently. One event/warning per register. Ensure that controller is not in sleep mode before reading.
of 148 34 Lock Mark symbol (screen locked when in Run Mode) 35 NOT IN AUTO 36 OFF FOR SILENCE 37 OFF FOR ALARM 38 POWER ON ECM... 39 WAITING ECM...
of 148 81 HIGH AUX ANALOG 2 warning 255 (0xFF) Empty – No message in queue 40108 Active Failure 0 ~ 44 R (Read Only) If the controller is in an active FAILURE mode the failure number in register 40108 corresponds to the below failure mode.
of 148 32 OPEN FUEL LEVEL 33 SHORT FUEL LEVEL 34 OPEN OIL LEVEL 35 SHORT OIL LEVEL 36 OPEN FUEL BASIN 37 SHORT FUEL BASIN 40 AUXILIARY FAIL 41 UNDER FREQUENCY 42 OVER FREQUENCY 162 USER CONFIG FAIL 1 163 USER CONFIG FAIL 2 176 OPEN AUX ANALOG 1 177 SHORT AUX ANALOG 1 178 LOW AUX ANALOG 1 179 HIGH AUX ANALOG 1 180 OPEN AUX ANALOG 2 181 SHORT AUX ANALOG 2 182 LOW AUX ANALOG 2 183 HIGH AUX ANALOG 2 255 (0xFF) Empty – No failure message 40109 System Sub-state delay countdown 0 ~ 65535 R The value of re
of 148 4. DIGITAL I/O AND ANALOG INPUTS (Read Only) Allows the status of the digital inputs and outputs to be read. Digital I/O and Analog Input will update every 1 second once. 40110 Digital Input 0 ~ 1023 R (Read Only) Status of controller digital inputs. OFF means the input is not active or not connected.
of 148 Bit2 = Output C 0 = OFF, 1 = ACTIVE Bit3 = Output D 0 = OFF, 1 = ACTIVE Bit4 = Output E 0 = OFF, 1 = ACTIVE Bit5 = Output F 0 = OFF, 1 = ACTIVE Bit6 = Output G 0 = OFF, 1 = ACTIVE Bit7 = Output H 0 = OFF, 1 = ACTIVE Bit8 = Extra Relay 0 = OFF, 1 = ACTIVE Bit9 = Fuel Relay 0 = OFF, 1 = ACTIVE Bit10 = Crank Rly 0 = OFF, 1 = ACTIVE Advanced Modbus register support 1. ENGINE-GENERATOR PARAMETERS (Read Only) Running parameters will update every 1 second.
of 148 100.0KPa 40156 Oil Level 0.0 ~ 100.0 R 1 bit equal to 0.1% % Reading 1000 corresponds to 100.0% 40157 Fuel In Basin 0 ~ 100.0 R 1 bit equal to 0.1% % Reading 1000 corresponds to 100.0% 40160 Line Voltage A-B 0~999.9 R 1 bit 0.1V V Reading 9999 V 40161 Line Voltage B-C R 40162 Line Voltage C-A R 40163 Phase Voltage A R V 40164 Phase Voltage B R V 40165 Phase Voltage C R V 40167 Phase A Current 0~999.9 V R 1 bit equal to 0.
of 148 40176 Current Run time 0 ~ 6553.5 R Hours 1 bit 0.1 hour (Total run time on active 65535 corresponds to running event). 6553.5Hs NOTE: Timer is reset to Zero after active running event has been terminated (OFF or AUTO mode waiting to start) 40177 ~ Engine Hours (old 40178 way – use registers 0~255999.9 R Total Accumulated Hours running hours, the reading in 40177, 1 bit 40172/40173 equal to 0.1 hour. The instead) reading in 40178, 1 bit equal to 1000 hours.
of 148 40148 Auxiliary Analog 2 0-6 R Type 0 = not available 1 = set to a switch 2 = Temperature in 0F 3 = Temperature in 0C 4 = Pressure in PSI 5 = Pressure in kPa 6 = Level (%) 40149 Auxiliary Analog 2 0 – 999.9 R Value 1 bit equal 0.1 unit Units depends on Reading 1000 the Type above. corresponds to 100.0 2. EVENTS HISTORY LOG 40130 Read Previous 0x6C93 Entry (27795) Read Next Entry 0x639C W Write control command to holding register address.
of 148 16 LOW COOLANT 17 OVER CRANK 18 OVER VOLTAGE 19 UNDER VOLTAGE 20 OVER CURRENT 21 EPS LOADS ERROR 22 LOW AIR PRESSURE 23 LOW HYDRAULIC 24 LOW OIL LEVEL 25 LOCKED ROTOR 26 HIGH BATTERY 27 LOSS OF ECM COMMUNICATION 28 OPEN ENG TEMPERATURE 29 SHORT ENG TEMPERATURE 30 OPEN OIL PRESSURE 31 SHORT OIL PRESSURE 32 OPEN FUEL LEVEL 33 SHORT FUEL LEVEL 34 OPEN OIL LEVEL 35 SHORT OIL LEVEL 36 OPEN FUEL BASIN 37 SHORT FUEL BASIN 40 AUXILIARY FAIL 41 UNDER FREQUENCY 42 OVER FREQUENCY 44 POWER ON 45 AUTO ENABLE
of 148 63 MODBUS START 162 (0xA2) CONFIG FAIL 1 163 (0xA3) CONFIG FAIL 2 176 OPEN AUX ANALOG 1 177 SHORT AUX ANALOG 1 178 LOW AUX ANALOG 1 179 HIGH AUX ANALOG 1 180 OPEN AUX ANALOG 2 181 SHORT AUX ANALOG 2 182 LOW AUX ANALOG 2 183 HIGH AUX ANALOG 2 233 (0xE9) DTC 235 (0xEB) System Recovery 40132 40133 40134 40135 Log Time stamp Decimal Minutes 0 ~ 59 Log Time stamp Decimal Hours 0 ~ 23 Log Time stamp Decimal Date 1 ~ 31 Log Time stamp Decimal Month 40136 Low 4-bit ones 0 ~ 9 Decimal
of 148 J1939 DIAGNOSTIC TROUBLE CODES Active DTC parameters will be updated and synchronized with front panel GSC400 display. Previously active DTC parameters will remain active even after they are read from the registers. Parameters can only be cleared once power is cycled to GSC400 controller or a shutdown is initiated.
of 148 reserved lamp status Bit 4~3 amber warning lamp status Bit 2~1 protect lamp status Low byte reserved for lamp status 40181 Previous Active DTC 0~65536 R 40182 No. 1 (Same format 0~65536 R as Active DTC registers above) 40183 ~ Registers 40183 to 40244 are not shown. 40244 They contain Previously Active DTC No. 2 to 32 and are in the same format as above. Same format as Active DTC registers above.
of 148 Appendix F J1939 Old DTC Conversion Methods This appendix was created to assist the user in decoding the information contained in the modbus DTC (DM1 and DM2) registers if the generator ECM does not support the newest DTC conversion method. The diagnostic trouble codes on J1939 are specified in a specific format. Older J1939 specifications had three conversion methods for the SPN and it was impossible to tell them apart from the DTC data alone. One had to consult the engine manufacturer.
of 148 Appendix G Additional Drawings The follow pages include various drawings that may be of benefit.
of 148