Function
Description
Exerciser
Enable
The exerciser is user selectable as enabled or disabled.
The exerciser enable allows for the automatic starting and
stopping of the engine.
Run Duration
The exerciser will automatically run the engine for a
specified duration. The run duration is user selectable from
10-240 minutes.
Pre-alarm
Delay
This is the delay time that the GSC400 will sound an
audible alert before the exerciser starts the engine. The
higher the delay setting the longer warning will be sounded
to anyone who may be around the engine.
Repeat freq
The exerciser is capable of automatically starting and
stopping the engine multiple times. The user may select
the repeat frequency according to the start hour and date.
The selectable range is between 0-672 hours.
Start Hour
The exerciser will automatically start the engine depending
upon the start hour setting
Start Date
The exerciser will automatically start the engine depending
upon the start date setting
4.4 – GSC400 Failure Log Screen
The GSC400 Failure Log screen may be
viewed to display GSC400 failure conditions.
A list of failures are displayed within the
GSC400 failure log screen. A total of 100
failure conditions are recorded and may be
viewed by scrolling through the list.
Date, times and descriptions of failure
condition are displayed. The “Get Failure
Log” button located in the bottom corner of
the Failure log screen window is used to
load the failure list stored in the GSC400 to
be displayed in the pc interface window.