4.3.8 – Misc
The GSC400 Misc screen allows
configuration to the following:
GSC400 Clock Settings:
1. Update time with windows time
Exercise Settings:
1. Exerciser Enable
2. Start Date
3. Start Hour
4. PreAlarm Delay
5. Run Duration
6. Repeat Freq.
Exerciser setup
Exerciser Enable Disable, enable
Run Duration 10-240 minutes
Pre-Alarm Delay 1-20 minutes
Repeat Frequency 1-672 hours
Start Hour 0-23
Start Date 1-31
The GSC400 clock settings may be set by pressing the “Update Clock with
Windows Time” button. The GSC400 Time and Date will be set as to the
Time/Date on the programming PC. The GSC400 has an internal power backup
which will power the Clock display while the controller is not powered by a DC power
source. If the controller is not power by the DC source for approx 3 weeks the controller
time will display 00:00:00. The “Update Clock with Windows Time” will need to be
initiated.