User manual

Installation and User Manual for the GSC400 PC Software Interface
15
Function
Description
Input Pin
Input 2-7 may be configured to a specific input. A specific
function can be assigned to more then one input pin to
allow a greater current output. If using a sender be careful
to select a Low or High input impedance location to
correspond to the sender specifications. Reserve may be
selected to configure proper setting without assigning an
active input.
Signal Source
How to obtain an engine failure.
The J1939 interface may be selected for a J1939 compliant
engine. The switch input may be selected for a mechanical
switch gauge types. Senders may be selected for electronic
gauge types.
Bypass Delay
When to recognize an engine failure. Bypass delay is the
time in seconds the GSC400 will wait after crank success
before checking engine for a failure input.
Switch Setting
When the Switch Input is selected as the signal source, the
switch setting can be configured for a ground or open
failure. Gnd means that ground would be a failure, +BAT
would be “Engine OK”. Open means that open switch
contacts would be “Failure”, and closed switch contacts
would be a “Engine OK”.
Shorted Sender
When the Sender Input is selected as the signal source, a
shorted sender can display a warning, shutdown the
engine or be set to have no effect (disabled).
Open Sender
When the Sender Input is selected as the signal source, an
open sender can display a warning, shutdown the engine
or be set to have no effect (disable).
Units
How to display warning and failure level values.
Warning Level
The value when using an electronic sender or J1939 input,
to initiating a warning.
Failure Level
The value when using an electronic sender or J1939 input,
to initiating a Failure.