User manual

Installation and User Manual for the GSC400 PC Software Interface
14
4.3.2 – Analog Inputs
The GSC400 Analog Input screen allows
configuration to the following inputs:
1. Hi Engine Temp
2. Oil Pressure
3. Fuel Level
4. Oil Level
5. Fuel in Basin
6. Low Engine Temp
Options for each parameter:
Specific
Input
Input Pin Reserve, Analog 2-7*
Signal Source J1939, Switch input, Sender
Bypass Delay 0-60 Seconds
Switch Setting GND = Fail, Open = Fail
Shorted Sender Disable, Warning, Shutdown
Open Sender Disable, Warning, Shutdown
Units selectable
Warning Level Adjustable
Failure Level Adjustable
*Analog inputs 2, 5, 6 and 7 are designed for high impedance senders.
Analog inputs 3 and 4 are designed for low impedance senders.