User manual

Installation and User Manual for the GSC400 PC Software Interface
13
Function
Description
Delay to Start
The time in seconds that the GSC400 will wait before
starting the generator.
Pre-heat Time
Time in seconds that the GSC400 will preheat the engine.
Preheat occurs before the engine cranking cycle.
Crank Time
Time in seconds the GSC400 will continue to crank the
generator. The controller will engage the flywheel until
engine start or the crank time expires.
MidHeat Time
Time in seconds that the GSC400 will preheat the engine.
Midheat occurs during the engine cranking cycle
Crank Rest Time
Time in seconds the GSC400 will wait between crank
attempts. If engine starting is unsuccessful after the
specific crank time, the starter will disengage for a specific
time period.
Crank Attempts
The number of crank attempts the GSC400 will perform
before going into over crack failure.
Fuel Crank Rest
This enables an energized fuel output while the controller is
in rest time.
False Restart
With this option enabled, when the engine goes into failure
before the oil bypass time has passed, the GSC400 will re-
attempt to start the generator.
Post-Heat Time
Time in seconds that the GSC400 will preheat the engine.
Post-heat occurs during the initial stage of engine run.
ETS On Duration Energize to stop. This output controls the fuel solenoid.
Warm-up Time
Time in seconds in order to allow the generator
sufficient time to warm up. This option must be enable in
order to be used.
Crank Disconnect
The frequency at which the GSC400 will disengage the
crank, keeping the fuel on to run the generator.
Cool Down Delay
Time in seconds the GSC400 will wait before shutting he
generator down under a no load condition in order to allow
engine cool down.
Crank Oil pres
This is the oil pressure which is exceeded during cranking.
Pressure: Used for locked rotor detection.