The GSC400 Update screen allows
configuration to the following parameters:
1. Engine Logic
2. Analog Inputs
3. Digital I/O
4. Battery
5. Speed
6. Generator
7. J1939
8. Misc
4.3.1 – Engine Logic
Engine Logic Settings:
Engine Logic
Delay to Start 0-60 seconds
Pre-heat Time 0-60 seconds
Crank Time 3-60 seconds
MidHeat Time 0-60 seconds
Crank Rest Time 1-60 seconds
Crank Attempts 1-60
Fuel Crank Rest Disable, Enable
False Restart Disable, Enable
Post-Heat Time 0-60 seconds
ETS On Duration 0-30 seconds
Warm-up Time 0-600 seconds
Crank Disconnect 100-2000 RPM
Cool Down Delay 0-600 seconds
Crank Oil pres 0-90 KPa