User manual
30 of 30
Constant Low oil
failures.
• Low oil level
• Choosing the sender setting
value to high, causing the
GSC300 to always fail since
the value of the sender is
always below the chosen
failure set point.
• Oil delay time needs to be
extended to eliminate false
failures.
• Faulty Sender
• Add oil
• Choose a lower sender
failure set point.
• Increase the delay time
from 0.5 to 6 seconds.
• Change out sender
Constant Temperature
failures.
• Low coolant level
• Choosing the sender setting
value to low, causing the
GSC300 to always fail since
the value of the sender is
always above the chosen
failure set point.
• Faulty Sender
• Add coolant
• Choose a higher sender
failure set point.
• Change out sender