Install Instructions

Series TE-OSA Outside Air Temperature Sensor
Specications - Installation and Operating Instructions
Bulletin T-TE-OSA
The Series TE-OSA Outside Air Temperature Sensor is designed to measure the
ambient air temperature on top of buildings and air handler units. The quick 1/4 turn lid
is captured by a chain to prevent the lid from being lost during installation and reduces
installation time by eliminating the need for tools. The internal terminal block gives a
reliable electrical connection and eliminates the need for wiring nuts. The Series TE-
OSA meets NEMA 3R requirements and is designed to be mounted on the north side
of the building to avoid radiated heat effects.
Figure A
SPECIFICATIONS
Accuracy: Thermistor temperature sensor: ±0.2°C @ 25°C (±0.36°F @ 77°F); RTD
temperature sensor: DIN class A: ±0.15°C @ 0°C (±0.28°F @ 32°F).
Temperature Limits: Operating: -40 to 302°F (-40 to 150°C).
Housing Material: Polycarbonate.
Enclosure Rating: NEMA 3R (IP54).
Weight: 4.2 oz.
4-39/64
[116.88]
4-1/32
[102.56]
4-9/32
[108.91]
4-25/32
[121.61]
6-1/4
[158.56]
1-1/2
[38.08]
1-17/32
[38.94]
IN ORDER TO USE THE PRODUCT IN
NEMA 3R CONDITIONS,
A 1/8˝ DRAIN HOLE MUST
BE DRILLED IN THE AREA INDICATED
When mounting in the vertical plane, a drain hole must be drilled
as shown in Figure A to meet NEMA 3 Ratings.
NOTICE
®
DWYER INSTRUMENTS, INC.
P.O. BOX 373 • MICHIGAN CITY, INDIANA 46360, U.S.A.
Phone: 219/879-8000
Fax: 219/872-9057
www.dwyer-inst.com
e-mail: info@dwyermail.com