Install Instructions

MAIN MENUS and SUB MENUS
SECr
(Security) MAIN MENU
SECr
is the only SUB MENU in the security MENU. When the security SUB MENU is selected, the present security
level is displayed in the upper right hand display. To change the security level, adjust the number displayed to the
number shown in the following table for the desired security level.
The password values shown in the table cannot be altered, so retain a copy of these pages for future reference.
OPEr
(Operation) MAIN MENU
The
OPEr
MENU selects the measurement type of the instrument.
The SUB MENUS are:
PrES
- Pressure
KFAC
- K Factor
XDIM
- X Dimension
UEL
- Velocity
ArEA
- Area
YDIM
- Y Dimension
FLO
- Flow
DIA
- Diameter
If the instrument is set for Velocity, the
OPEr
MENU will have an additional
KFAC
SUB MENU. If the instrument is
set for Flow, the
OPEr
MENU will have additional
KFAC
and
ArEA
SUB MENUS. These will be discussed under
Velocity and Flow. When scrolling through the
OPEr
SUB MENUS, the measurement type the unit is currently set
for will show the units in the upper right display. The other measurement types will have a blank upper right display.
Security Level
Displayed Access
Password
Value to Enter
1 All menus access 10
2 Menu Access
SP/AL Locked
70
3 SP/AL Access
Menus Locked
90
4 All settings locked 111
Units visible, so unit
is presently set to
measure pressure
Units not visible Units not visible