Analog Panel Meter  Instruction Manual 
9 
ISOLATED 
TRANSMITTER 
POWER SUPPLY 
Terminals P+ & P-: 24 VDC  10%. 12/24 VDC powered models 
selectable for 24, 10, or 5 VDC supply (internal jumper J4). 
85-265 VAC models rated @ 200 mA max, 12/24 VDC powered 
models rated @ 100 mA max, @ 50 mA max for 5 or 10 VDC 
supply. 
NORMAL MODE 
REJECTION 
Greater than 60 dB at 50/60 Hz 
ISOLATION 
4 kV input/output-to-power line 
500 V input-to-output or output-to-P+ supply 
OVERVOLTAGE 
CATEGORY 
Installation Overvoltage Category II: 
Local level with smaller transient overvoltages than 
Installation Overvoltage Category III. 
ENVIRONMENTAL 
Operating temperature range: -40 to 65°C 
Storage temperature range: -40 to 85°C 
Relative humidity: 0 to 90% non-condensing 
CONNECTIONS 
Removable screw terminal blocks accept 12 to 22 AWG 
wire, RJ45 for external relays, digital I/O, and serial 
communication adapters. 
ENCLOSURE 
1/8 DIN, high impact plastic, UL 94V-0, color: black 
MOUNTING 
1/8 DIN panel cutout required: 
3.622" x 1.772" (92 mm x 45 mm) 
Two panel mounting bracket assemblies are provided. 
TIGHTENING 
TORQUE 
Screw terminal connectors: 5 lb-in (0.56 Nm) 
OVERALL 
DIMENSIONS 
4.68" x 2.45" x 5.64" (119 mm x 62 mm x 143 mm) 
(W x H x D) 
WEIGHT 
9.5 oz (269 g) 
WARRANTY 
3 years parts & labor 
Process Input 
INPUTS 
Field selectable: 
0-20, 4-20 mA, 10 V (0-5, 1-5, 0-10 V), Modbus PV 
(Slave) 
ACCURACY 
±0.03% of calibrated span ±1 count, 
square root & programmable exponent accuracy range: 
10-100% of calibrated span 
TEMPERATURE 
DRIFT 
0.005% of calibrated span/C max from 0 to 65C ambient, 
0.01% of calibrated span/C max from -40 to 0C ambient 
SIGNAL INPUT 
CONDITIONING 
Linear, square root, programmable exponent, or round 
horizontal tank volume calculation 