Analog Panel Meter  Instruction Manual 
83
Meter Copy or Cloning Instructions
Caution! 
Do not connect the two meters to 
the same signal source while 
cloning. Internal calibration may 
be affected. 
 Copy Function Requirements 
To successfully copy settings from one meter to another, both meters 
must have the same software version and same baud rate setting, See 
Determining Software Version, page 86 for instructions. 
1.  Connect two meters using a PMA-02 meter copy cable. 
Warning! 
Use PMA-02 meter copy cable only! 
Using standard CAT5 or other cable will cause 
damage to both meters. 
2.  Do not connect the two meters to the same signal source. 
3.  Power up both meters. Leave Clone meter in Run Mode. 
4. Enter the Advanced Features menu of the Master meter see 
Advanced Features Menu page 69. 
5. Scroll to the Copy function using the Up arrow button then press 
Enter. 
6.  The meter displays the message Send. Press Enter, the display 
flashes while sending data. The message done is displayed when 
copying is completed. 
7.  The Clone meter displays the message CPY rC while being 
programmed, then the message done when copying is completed. 
The meter initializes and returns to Run Mode using the same 
settings as the Master. 
8.  If meter to be cloned does not respond to the data being sent, refer 
to Copy Function Requirements above. 
!