Manual
Analog Panel Meter  Instruction Manual 
80 
Tare (tare) 
The tare function zero’s out the display. In the case of scale weight, tare 
is used to eliminate container weight and provide net weight readings. 
There are two tare functions; Capture Tare and Reset Tare. 
When the capture tare function is used, the display reading is offset by 
the displayed amount to make the displayed value zero. This modified 
display value is the net value. The originally displayed value without the 
tare offset is the gross value. Both may be chosen as a display option. 
Reset tare removes the display offset of the net value, and the gross and 
net values become the same until a new capture tare is entered. 
This function may only be used when Total (
total) is set to No (no). 
Internal Source Calibration (ICAL) 
The meter is factory calibrated prior to shipment to read in milliamps and 
volts, depending on the input selection. The calibration equipment is 
certified to NIST standards. 
The use of calibrated signal sources is necessary to calibrate the 
internal source of the meter. The meter’s internal source is what allows 
the user to scale the meter without applying a signal. 
Check calibration of the meter at least every 12 months. Each input must 
be recalibrated separately. 
Notes: 
1.  If meter is in operation and it is intended to 
accept only one input type (e.g. 4-20 mA), 
recalibration of other input is not necessary. 
2.  Allow the meter to warm up for at least 
15 minutes before performing the internal 
source calibration procedure. 
0.0
lbs
0.
lbs
0.2 
lbs
Before tare 
A
fter capture tare
After reset tare