SPECIFICATIONS 
Except where noted all specifications apply to operation at +25°C. 
General 
DISPLAY 
Upper display: 0.6" (15 mm) high, red LEDs 
Second display: 0.46" (12 mm) high, red LEDs 
6 digits: each (-99999 to 999999), with lead zero blanking. 
DISPLAY 
INTENSITY 
Eight user selectable intensity levels 
DISPLAY 
UPDATE RATE 
5/second (200 ms) 
OVERRANGE 
Display flashes 
999999 
UNDERRANGE 
Display flashes 
-99999 
DISPLAY 
ASSIGNMENT 
The main (Big) and small (Little) displays may be assigned 
to rate, total, grand total, alternate (rate/total, rate/grand 
total, rate/units, total/units, and grand total/units), set points, 
max/min, units (lower display only), and Modbus input. 
Additional displays are available if parameter total is off, 
and parameter d-SCAL is on: gross, alternating gross/net, 
PV1, PV2, and PCT (refer to MPM instruction manual found 
on www.dwyer-inst.com). 
PROGRAMMING 
METHODS 
Four front panel buttons, digital inputs, PC and Panel Meter 
Pro software, or cloning using Copy function. 
NOISE FILTER 
Programmable from 2 to 199 (0 will disable filter) 
FILTER BYPASS 
Programmable from 0.1 to 99.9% of calibrated span 
RECALIBRATION 
All ranges are calibrated at the factory. Recalibration is 
recommended at least every 12 months. 
MAX/MIN 
DISPLAY 
Max/min readings reached by the process are stored until 
reset by the user or until power to the meter is turned off. 
PASSWORD 
Three programmable passwords restrict modification of 
programmed settings and two prevent resetting the totals. 
Pass 1: Allows use of function keys and digital inputs 
Pass 2: Allows use of function keys, digital inputs and editing set/reset points 
Pass 3: Restricts all programming, function keys, and digital inputs. 
Total: Prevents resetting the total manually 
Gtotal: Prevents resetting the grand total manually
NON-VOLATILE 
MEMORY 
All programmed settings are stored in non-volatile memory 
for a minimum of ten years if power is lost. 
POWER 
OPTIONS 
85-265 VAC 50/60 Hz, 90-265 VDC, 20 W max 
or jumper selectable 12/24 VDC  10%, 15 W max 
FUSE  Required external fuse: UL Recognized, 5 A max, slow 
blow; up to 6 meters may share one 5 A fuse 