Analog Output Programming (AoutPr) 
The Analog Output Programming menu is used to program the behavior 
of the 4-20 mA output. The following parameters and functions are 
programmed in this menu: 
1.  Source: Source for generating the 4-20 mA output (e.g. PV) 
2.  Overrange: Analog output value with display in overrange condition 
3.  Underrange: Analog output value with display in underrange condition 
4.  Break: Analog output value when loop break is detected 
5.  Max: Maximum analog output value allowed regardless of input 
6.  Min: Minimum analog output value allowed regardless of input 
7.  Calibrate: Calibrate the internal 4-20 mA source reference used to 
scale the 4-20 mA output 
Analog Output Source 
The source for generating the 4-20 mA output may be assigned to the 
rate/process variable, total, grand total, maximum or minimum value 
reached by the rate/process, or one of the set points, or the Modbus PV 
input. 
Analog Output Calibration 
To perform the analog output calibration it’s recommended to use a 
milliamp meter with a resolution of at least 0.1 µA to measure the output 
current. The values saved internally during this procedure are used for 
scaling the 4-20 mA output in the 
Setup menu. 