Analog Panel Meter  Instruction Manual 
71 
Display Parameter  Action/Setting 
O-rang 
Overrange
Program mA output for display overrange
u-rang 
Underrange
Program mA output for display underrange
Break 
Loop Break 
Set relay condition if loop break detected 
Force 
Force 
Force analog output value for loop break
Ignore 
Ignore 
Ignore loop break condition
mAx 
Maximum 
Program maximum mA output allowed 
min 
Minimum 
Program minimum mA output allowed 
Calib 
Calibrate 
Calibrate 4-20 mA output (internal 
reference source used for scaling the 
output) 
4 mA 
4 mA output 
Enter mA output value read by milliamp 
meter with at least 0.001 mA resolution 
20 mA 
20 mA output 
Enter mA output value read by milliamp 
meter with at least 0.001 mA resolution 
user 
User I/O
Assign function keys and digital I/O
F1 
F1 function key 
Assign F1 function key 
F2 
F2 function key 
Assign F2 function key 
F3 
F3 function key 
Assign F3 function key 
F4 
F4 function 
Assign F4 function (digital input) 
dI I 
Digital input 1 
Assign digital input 1 – 8, if expansion 
modules are connected 
dO 1 
Digital output 1 
Assign digital output 1 – 8, if expansion 
modules are connected 
ICal 
Internal source 
calibration 
Enter internal source calibration (used for 
scaling the meter without a signal source 
C CAL 
Current 
calibration 
Calibrating 4-20 mA current input (internal 
reference source used for scaling the input) 
C lo 
Current low 
Calibrate low current input (e.g. 4 mA) 
C Hi 
Current high 
Calibrate high current input (e.g. 20 mA) 
v CAL 
Voltage 
calibration
Calibrating voltage input 
v Lo 
Voltage low 
Calibrate low voltage input (e.g. 0 V) 
v Hi 
Voltage high
Calibrate high voltage input (e.g. 10 V)
Copy 
Cop
y
Enter copy function 
send 
Send 
Send meter settings to another meter 
done 
Done 
Copy function completed 
Diag 
Diagnostics 
Display parameter settings 