Analog Panel Meter  Instruction Manual 
59 
Non-Latching Relay (Auto) 
Automatic reset only 
Condition LED Relay
Normal Off Off 
Alarm On On 
Ack (No effect)  On  On 
Normal Off Off 
In this application, the meter is set up for automatic reset (non-latching 
relay). Acknowledging the alarm while it is still present has no effect on 
either the LED or the relay. When the alarm finally goes away, the relay 
automatically resets and the LED also goes off. 
Non-Latching Relay (A-nman) 
Automatic + manual reset at any time 
Condition LED Relay
Normal Off Off 
Alarm On On 
Normal Off  Off 
Next Alarm  On  On 
Ack  On  Off 
Normal Off Off 
In this application, the meter is set up for automatic and manual reset at 
any time (non-latching relay). The LED and the relay automatically reset 
when the meter returns to the normal condition. 
The next time an alarm occurs, the operator acknowledges the alarm 
manually while the alarm condition still exists. This causes the relay to 
reset, but the LED stays on until the meter returns to the normal 
condition. 
Latching Relay (LatcH) 
Manual reset any time 
Condition LED Relay
Normal Off Off 
Alarm On On 
Ack Off Off 
In this application, the meter is set up for manual reset at any time. 
Acknowledging the alarm even if the alarm condition is still present 
resets the relay and turns off the LED. 