Manual
Analog Panel Meter  Instruction Manual 
40 
Scaling the Meter (SCALE) 
The process inputs (4-20 mA and 10 VDC) can be scaled to display the 
process variable in engineering units. 
A signal source is not needed to scale the meter; simply program the 
inputs and corresponding display values. 
For instructions on how to program numeric 
values see 
Setting Numeric Values, page 34. 
Error Message (Error) 
An error message indicates that the calibration or scaling process was not 
successful. 
After the error message is displayed, the meter reverts to the input prior 
to the failure during calibration or scaling and to input 1 during internal 
calibration, allowing the appropriate input signal to be applied or 
programmed. 
The error message might be caused by any of the following conditions: 
1.  Input signal is not connected to the proper terminals or it is connected 
backwards. 
2.  Wrong signal selection in 
Setup menu. 
3.  Minimum input span requirements not maintained. 
4.  Input 1 signal inadvertently applied to calibrate input 2. 