Manual
Analog Panel Meter  Instruction Manual 
26 
Figure 18: Digital I/O Module Connections 
Interlock Relay Feature 
As the name implies, the interlock relay feature reassigns one, or more, 
alarm/control relays for use as interlock relay(s). Interlock contact(s) are 
wired to digital input(s) and trigger the interlock relay. This feature is 
enabled by configuring the relay, and relative digital input(s) (see page 
64). In one example, dry interlock contacts are connected in series to 
one digital input which will be used to force on (energize) the assigned 
interlock power relay when all interlock contacts are closed (safe). The 
interlock relay front panel LED flashes when locked out. The interlock 
relay would be wired in-series with the load (N/O contact). See below. 
Figure 19. Interlock Connection 
123456
+5 I1 I2 I3 I4 O1
78
O2 O3
910
O4 G
DI 1-4 DO 1-4
5 VDC GND