Manual
Analog Panel Meter  Instruction Manual 
13 
Modbus
®
 RTU Serial Communications 
SLAVE ID 
1 – 247 (Meter address) 
BAUD RATE 
300 - 19,200 bps 
TRANSMIT 
TIME DELAY 
Programmable between 0 and 199 ms 
DATA 
8 bit (1 start bit, 1 or 2 stop bits) 
PARITY 
Even, Odd, or None with 1 or 2 stop bits 
BYTE-TO-BYTE 
TIMEOUT 
0.01 – 2.54 second 
TURN AROUND 
DELAY 
Less than 2 ms (fixed) 
Note: Refer to the Modbus Register Tables located at www.dwyer-inst.com for 
details. 
PMA-12 Digital Input & Output Expansion Module 
CHANNELS 
4 digital inputs & 4 digital outputs per module 
SYSTEM 
Up to 2 modules for a total of 8 inputs & 8 outputs 
DIGITAL INPUT 
LOGIC HIGH 
3 to 5 VDC 
DIGITAL INPUT 
LOGIC LOW 
0 to 1.25 VDC 
DIGITAL OUTPUT 
LOGIC HIGH 
3.1 to 3.3 VDC 
DIGITAL OUTPUT 
LOGIC LOW 
0 to 0.4 VDC 
SOURCE 
CURRENT 
10 mA maximum output current 
SINK 
CURRENT 
1.5 mA minimum input current 
+5 V 
TERMINAL 
To be used as pull-up for digital inputs only 
Connect normally open pushbuttons across +5 V & DI 1-4. 