Manual
Analog Panel Meter  Instruction Manual 
12 
RELAY RESET 
User selectable via front panel buttons, digital inputs, or PC
1.  Automatic reset only (non-latching), when the input 
passes the reset point or total is reset to zero. 
2.  Automatic + manual reset at any time (non-latching) 
3.  Manual reset only, at any time (latching) 
4.  Manual reset only after alarm condition has cleared 
(latching) 
Note: Front panel button or digital input may be assigned to 
acknowledge relays programmed for manual reset. 
TIME DELAY 
0 to 999.9 seconds, on & off relay time delays 
Programmable and independent for each relay. 
FAIL-SAFE 
OPERATION 
Programmable and independent for each relay. 
Note: Relay coil is energized in non-alarm condition. 
In case of power failure, relay will go to alarm state. 
AUTO 
INITIALIZATION 
When power is applied to the meter, relays will reflect the 
state of the input to the meter. 
Isolated 4-20 mA Transmitter Output 
OUTPUT 
SOURCE 
Rate/process, total, grand total, max, min, set points 1-8, or 
manual control mode 
SCALING RANGE 
1.000 to 23.000 mA for any display range. 
CALIBRATION 
Factory calibrated: 4.000 to 20.000 = 4-20 mA output 
ANALOG OUT 
PROGRAMMING 
23.000 mA maximum for all parameters: 
Overrange, underrange, max, min, and break 
ACCURACY 
± 0.1% FS ± 0.004 mA 
TEMPERATURE 
DRIFT 
0.4 µA/C max from 0 to 65C ambient, 
0.8 µA/C max from -40 to 0C ambient
Note: Analog output drift is separate from input drift.
ISOLATED 
TRANSMITTER 
POWER SUPPLY 
Terminals I+ & R: 24 VDC  10%. May be used to power the 
4-20 mA output or other devices. Refer toFigure 5 on page 
19 and Figure 15 on page 24. 
All models rated @ 40 mA max. 
EXTERNAL LOOP 
POWER SUPPLY 
35 VDC maximum 
OUTPUT LOOP 
RESISTANCE 
Power supply  Minimum  Maximum 
24 VDC 
10  700  
35 VDC (external) 
100  1200  