Analog Panel Meter  Instruction Manual 
11 
TOTAL 
OVERFLOW 
OVERRIDE 
Program total reset for automatic with 0.1 second delay 
and set point 1 for 999,999 
TOTALIZER 
PRESETS 
Up to eight, user selectable under setup menu. Any set 
point can be assigned to total and may be programmed 
anywhere in the range of the meter for total alarm 
indication. 
PROGRAMMABLE 
DELAY 
ON RELEASE 
0.1 and 999.9 seconds; applied to the first relay assigned 
to total or grand total. 
If the meter is programmed to reset total to zero 
automatically when the preset is reached, then a delay will 
occur before the total is reset. 
TOTAL RESET 
Via front panel button, external contact closure on digital 
inputs, automatically via user selectable preset value and 
time delay, or through serial communications. 
TOTAL RESET 
PASSWORD 
Total and grand total passwords may be entered to 
prevent resetting the total or grand total from the front 
panel. 
NON-RESETTABLE 
TOTAL 
The grand total can be programmed as a non-resettable 
total by entering the password “050873”. 
Caution!
Once the Grand Total has been programmed 
as “non-resettable” the feature cannot
 be 
disabled. 
Relays 
RATING 
2 or 4 SPDT (Form C) internal and/or 4 SPST (Form A) 
external; rated 3 A @ 30 VDC and 125/250 VAC resistive 
load; 1/14 HP (≈ 50 W) @ 125/250 VAC for inductive loads 
NOISE 
SUPPRESSION 
Noise suppression is recommended for each relay contact 
switching inductive loads; see page 23 for details. 
RELAY 
ASSIGNMENT 
Relays may be assigned to rate, total, or grand total. 
DEADBAND 
0-100% of span, user programmable 
HIGH OR LOW 
ALARM 
User may program any alarm for high or low trip point. 
Unused alarm LEDs and relays may be disabled (turn off). 
RELAY 
OPERATION 
Automatic (non-latching) and/or manual reset 
Latching (requires manual acknowledge) with/without clear
Pump alternation control (2 to 8 relays) 
Sampling (based on time) 
Off (disable unused relays and enable Interlock feature) 
Manual on/off control mode 
!