Manual
Analog Panel Meter  Instruction Manual 
10 
MULTI-POINT 
LINEARIZATION 
2 to 32 points 
PROGRAMMABLE 
EXPONENT 
1.0001 to 2.9999 
ROUND H TANK 
Diameter & Length: 999.999 inch or cm calculates volume 
in gallons or liters respectively. 
LOW-FLOW 
CUTOFF 
0-999999 (0 disables cutoff function) 
DECIMAL POINT 
Up to five decimal places or none: 
d.ddddd, d.dddd, d.ddd, d.dd, d.d, or dddddd 
CALIBRATION 
RANGE 
Input 
Range 
Minimum Span 
Input 1 & Input 2 
4-20 mA  0.15 mA
10 V 
0.10 V 
An error message will appear if the input 1 and input 2 
signals are too close together. 
INPUT 
IMPEDANCE 
Voltage ranges: greater than 500 k 
Current ranges: 50 - 100  
(depending on resettable fuse 
impedance)
INPUT 
OVERLOAD 
Current input protected by resettable fuse, 30 VDC max. 
Fuse resets automatically after fault is removed. 
F4 DIGITAL INPUT 
CONTACTS 
3.3 VDC on contact. Connect normally open contacts 
across F4 to COM. 
F4 DIGITAL INPUT 
LOGIC LEVELS 
Logic High: 3 to 5 VDC 
Logic Low: 0 to 1.25 VDC 
Rate/Totalizer 
RATE DISPLAY 
INDICATION 
-99999 to 999999, lead zero blanking. “R” LED illuminates 
while displaying rate. 
TOTAL DISPLAY 
& TOTAL 
OVERFLOW 
0 to 999,999; automatic lead zero blanking. “T” LED is 
illuminated while displaying total or grand total. 
Up to 999,999,999 with total-overflow feature. “
oF” is 
displayed to the left of total overflow and ▲ LED is 
illuminated. 
TOTAL 
DECIMAL POINT 
Up to five decimal places or none: 
d.ddddd, d.dddd, d.ddd, d.dd, d.d, or dddddd 
Total decimal point is independent of rate decimal point. 
TOTALIZER 
Calculates total based on rate and field programmable 
multiplier to display total in engineering units. Time base 
must be selected according to the time units in which the 
rate is displayed. 
TOTALIZER 
ROLLOVER 
Totalizer rolls over when display exceeds 999,999,999. 
Relay status reflects display. 