Maintained Alarm (ACK before RESET)
Condition LED Horn
1
st
Pt Next Pt
Normal
Off Off Off
Alert
Intermittent Flash Fast Flash On
ACK Pushbutton
Acknowledge
Slow Flash Steady Off
RESET Pushbutton
1
st
Out Reset
Steady Steady Off
Normal
Off Off Off
Sequence F3A Flowchart Sequence F3A
Switch Positions
Reset
Pressed
Condition Normal
1
st
Pt LED Off
Next Pt LED Off
Horn Off
Condition Alert
1
st
Pt LED Intermittent Flash
Next Pt LED Fast Flash
Horn On
larm Condition
Ack while
Normal
Reset
Pressed
Condition Any
1
st
Pt LED Fast Flash
Next Pt LED Fast Flash
Horn On
A
ck while
Normal
Condition Alert
1
st
Pt LED Steady
Next Pt LED Steady
Horn Off
Condition Normal
1
st
Pt LED Slow Flash
Next Pt LED Off
Horn Off
Condition Alert
1
st
Pt LED Slow Flash
Next Pt LED Steady
Horn Off
Ack while
Alarmed
A
ck while
A
larmed
Return
to Normal
Return