User guide

AN24 & AN28 Annunciators Instruction Manual
32
ISA Sequence A
Acknowledge Pushbutton and Automatic Reset
Momentary Alarm Maintained Alarm
Sequence A Sequence A Flowchart
Switch Positions
Condition LED Horn Condition LED Horn
Normal
Off Off
Normal
Off Off
Alert
Flash On
Alert
Flash On
Normal
Flash On
ACK Pushbutton
ACK Pushbutton
Acknowledge
Steady Off
Acknowledge
Off Off
Normal
Off Off
Condition Normal
LED Off
Horn Off
Condition Alert
LED Flash
Horn On
Condition Alert
LED Steady
Horn Off
larm Condition
Ack when
In
p
uts Normal
Return
to Normal
Ack
Pressed
Relay Operation
For complete details on relay function, see page 24.
Relay 1: Operation
Relay 1 enters alarm state when there is a new alarm. This relay will clear
when the alarms are acknowledged.
Relay 2 Operation
Relay 2 enters alarm state when any channel displays in alarm state. This
relay will clear when all indication LEDs are cleared.