User guide
AN24 & AN28 Annunciators Instruction Manual
25
Relay Fail-Safe Programming Example
The following is an example of relay fail-safe setup. Relays 1 and 2 are
changed from the default settings of normal operation to fail-safe
operation.
1. Press and hold ACK and RESET for 3 seconds. When all
LEDs cycle, release.
2. Press RESET within 3 seconds of release while LEDs cycle.
All LEDs blink in unison.
3. Press RESET again within 3 seconds while LEDs blink
4. LED 1 will be off indicating
normal operation of relay 1.
LEDs 2 through 4 will be dim.
5. Press Reset to change LED 1
from off to on, setting relay 1
for fail-safe operation.
6. Press ACK to confirm the
setting for relay 1and proceed
to program relay 2.
7. Press RESET to change LED 2
from off to on, setting relay 2
for fail-safe operation.
8. Press ACK to confirm the setting for relay 2.
9. Press and hold ACK for 5 seconds to return to normal
operation.
Note: LEDs 3 and 4 are used for the silence pushbutton enable/disable
option (see page 27) and no lock-in option (see page 27)