Owner manual

P
arameter Mode (PARAM)
P
arameter Types
T
here are four parameter modes: Dead Zone, KP, KI, and KD.
T
hese values are reflected as soon as they are changed, therefore the appropriate
values are found by checking the valve’s motion in real time.
Adjustment of Dead Zone (dEAdZONE)
T
his is the range of error % that the positioner is not adjusted. Hunting or oscillation
d
ue to friction between the stem and packing is prevented by this parameter.
1
. Press and hold <ENTER> at RUN mode for 6 seconds and AUTO CAL
m
essage appears.
2. Scroll with <DOWN> until PARAM mode is displayed.
3. Push <ENTER> and dEAdZONE mode is displayed.
4. Push <ENTER> again and *EAdZONE message appears.
5
. Adjust dEAdZONE value by pushing <UP> or <DOWN>. Adjusted valued is
a
pplied immediately without additional operation. Users can easily check its
a
djustment by changing the current input signal to the positioner. Optimum
control value is found by adjusting values during the valve operation.
6. Push <ENTER> to save the value. +EAdZONE message appears on LCD.
7. Push <ESC> to exit dEAdZONE mode.
KP
1. Press and hold <ENTER> at RUN mode for 6 seconds and AUTO CAL
message appears.
2. Scroll with <DOWN> until PARAM mode is displayed.
3. Push <ENTER> and dEAdZONE mode is displayed.
4. Scroll with <DOWN> until KP mode is displayed.
5. Push <ENTER> at KP mode and *KP message appears on LCD.
6. Adjust KP value with <UP> or <DOWN>. Adjusted value is applied immediately
without additional operation. Users can easily check its adjustment by changing
the current input signal to the positioner. Optimum control value is found by
adjusting the values during valve operation.
7. Push <ENTER> to save the value and +KP message appears on LCD.
8. Push <ESC> to exit KP mode.
PT
1. Press and hold <ENTER> at RUN mode for 6 seconds and AUTO CAL
message appears.
2. Scroll with <DOWN> until PARAM mode is displayed.
3. Push <ENTER> and dEAdZONE mode is displayed.
4. Scroll with <DOWN> until PT mode is displayed.
5. Push <ENTER> at PT mode and *PT message appears on LCD.
6. Adjust PT value with <UP> or <DOWN>. Adjusted value is applied immediately
without additional operation. Users can easily check its adjustment by changing
the current input signal to the positioner. Optimum control value is found by
adjusting the values during valve operation.
7. Push <ENTER> to save the value and +PT message appears on LCD.
8. Push <ESC> to exit KP mode.
H
AND CAL
W
hen auto calibration is started, Series 185 and 285 positioners set zero points
a
nd end points based on full stroke. HAND CAL allows for user defined zero and
e
nd points.
Hand Calibration Types
PV_ZERO: Edit mode to change the zero point of valve.
P
V_END: Edit mode to change the end point of a valve.
T
R_ZERO: Edit mode to change the zero point of transmitter.
T
R_END: Edit mode to change the end point of transmitter.
Adjustment of valve zero point (1 to 5) and end point (6 to 10).
PV_ZERO
1
. Press and hold <ENTER> at RUN mode for 6 seconds and AUTO CAL
m
essage appears.
2
. Scroll with <DOWN> until HAND CAL mode is displayed.
3. Push <ENTER> and PV_ZERO mode is displayed.
4. Push <ENTER> at PV_ZERO mode and *PZ mode is started. The valve stem
will move automatically to the current zero point. On the LCD, the valve stroke
is displayed as 0%. *PZ indicates the zero point is ready to be set.
5
. Adjust valve stem by pushing <UP> or <DOWN>. When valve stem is at the
d
esired zero point, save it by pushing <ENTER>.
6
. Push <ESC> to exit PV_ZERO mode.
PV_END
1. To change valve end point, scroll with <DOWN> at HAND CAL menu and select
PV_END.
2
. Push <ENTER> at PV_END mode and *PE mode is displayed. The valve stem
w
ill move automatically to the current end point. On the LCD, the valve stroke
i
s displayed as 100%. *PE indicates the end point is ready to be set.
3. Adjust valve stem by pushing <UP> or <DOWN>. When the valve stem is at
the desired end point, save it by pushing <ENTER>.
4. Push <ESC> to exit PV_END mode.
<ENTER>
6 seconds
<ENTER>
6 seconds
<ENTER>
<ENTER> <UP>/<DOWN>
then <ENTER>
<ESC>
3 times
COMPLETED
<ENTER> <DOWN>
3 times
<ENTER>
<UP>/<DOWN>
then <ENTER>
<ESC>
3 times
COMPLETED
<ENTER> <DOWN>
7 times
<ENTER>
<UP>/<DOWN>
then <ENTER>
<ESC>
3 times
COMPLETED
<
ENTER>
6
seconds
<
DOWN>
3
times
<
ENTER>
<ENTER> <UP>/<DOWN>
then <ENTER>
<ESC>
<DOWN> <ENTER> <UP>/<DOWN>
then <ENTER>
<ESC>
COMPLETED