Owner manual

W
arning Code
T
his code is displayed when the positioner control is available but there is a
p
ossibility of malfunction or low accuracy. Code B, F, G, H applies.
M
AINTENANCE/REPAIR
U
pon final installation of the Series 185/285, no routine maintenance is required.
T
he Series 185/285 is not field serviceable and should be returned if repair is
n
eeded. Field repair should not be attempted and may void warranty.
WARRANTY/RETURN
Refer to “Terms and Conditions of Sales” in our catalog and on our website. Contact
c
ustomer service to receive a Return Goods Authorization number before shipping
t
he product back for repair. Be sure to include a brief description of the problem
p
lus any additional application notes.
DWYER INSTRUMENTS, INC.
Phone: 219/879-8000 www.dwyer-inst.com
P.O. BOX 373 MICHIGAN CITY, INDIANA 46360, U.S.A. Fax: 219/872-9057 e-mail: info@dwyer-inst.com
©Copyright 2013 Dwyer Instruments, Inc. Printed in U.S.A. 6/13 FR# RB-443952-00 Rev. 2
W
arning Code
B
F
G
H
Code Description and Cause
PV end-PV zero range is below
5
00. The angle of feedback
l
ever is too small.
Time elapsed for either full-open
or full-close is less than 1
s
econd.
T
he size of the actuator is
t
oo small.
P
v zero is below 100.
The angle of feedback lever
is too large.
Pv end is over 4000.
T
he angle of feedback lever
i
s too large.
Action
R
e-install/mount the positioner.
M
ake sure the feedback lever
d
oes not touch the stopper at
b
oth 0 and 100%.
After re-installation, perform 
AUTO1 calibration.
Use variable orifice.
R
eplace actuator with larger
c
apacity.
Re-install/mount the positioner.
After re-installation, perform
AUTO1 calibration.
R
e-install/mount the positioner.
A
fter re-installation, perform
A
UTO1 calibration.
Used timeUser Set
ENT
: Enter button
Manual Mode
Auto 2
Auto cal
RUN Mode
E
NT
(5 sec)
E
SC
ESC
Auto 1
E
NT
BIAS
Auto 3
E
SC
ESC
V_O
E
SC
E
SC
Hart ver.CharacterK P
End point
ViewValveHand calParameter
ESCESC ESC ESCESC
ESC
Start point
Dead Zone
ESC ESC
E
NT
E
NT
ESC
Sof ver.
RA / DA
E
NT
E
NT
BIAS
Tight shut onTR end point
K D
Tight shut oTR start point
K I
E
SC
E
SC
E
SC
ESC ESCESC
Polling Add
E
SC
ESC
E
SC
E
SC
E
SC
E
SC
I value
Split control
E
SC
E
SC
: Up button
ESC
: Down button
: Esc button
Error code
Full close time
ESC
Full open time
ESC
ESC
View method
ESC
ESC
ESC
ESC
E
SC
K I_
K P_
ESC
K D_
F
irmware MAP