Instruction manual
Analog Panel Meter Instruction Manual
82
Tips:
Low and high input signals can be any valid values within the
range of the meter.
Observe minimum input span requirements between input 1
and input 2.
Low input should be less than high input signal.
Error Message (Error)
An error message indicates that the calibration or scaling process was not
successful.
After the error message is displayed, the meter reverts to the input prior
to the failure during calibration or scaling and to input 1 during internal
calibration, allowing the appropriate input signal to be applied or
programmed.
The error message might be caused by any of the following conditions:
1. Input signal is not connected to the proper terminals or it is
connected backwards.
2. Wrong signal selection in
Setup menu.
3. Minimum input span requirements not maintained.
4. Input 1 signal inadvertently applied to calibrate input 2.
Minimum Input Span
The minimum input span is the minimum difference between input 1 and
input 2 signals required to complete the calibration or scaling of the meter.
Input range Input 1 & input 2 span
4-20 mA 0.15 mA
10 VDC
0.10 VDC
Meter Copy Function (Copy)
The Copy function is used to copy (or clone) all the settings from one
meter to other meters requiring exactly the same setup and
programming (
i.e. type of input, scaling, decimal pt., filter, bypass, etc.).
Warning!
Only the PMA-02 meter copy cable must be used for
meter-to-meter interfacing. The PMA-02 is a special
eight-conductor flat cable with two wires swapped.
Using standard CAT5 or other cable will cause
damage to both meters.