Setting the Input Signal (Input)
Enter the Input menu to set up the meter to display current (mA) or
voltage (
volt) inputs.
The current input is capable of accepting any signal from 0 to 20 mA.
Select current input to accept 0-20 mA or 4-20 mA signals.
The voltage input is capable of accepting any signal from -10 to +10 VDC.
Select voltage input to accept 0-5, 1-5, 0-10, or
10 VDC signals.
Setting the Totalizer Features (total)
To simply not display the total, select alternative display parameters in
the display (
dsplay) menu.
Enable or disable the totalizer features by selecting “
Yes” or “no” after
the input type has been set up. If the totalizer features are disabled, all
the totalizer features and functions are hidden from the menus. Level
and process meter features and functions are added to the menus.
If disabling the
total parameter by selecting no, please refer to the
MPM manual available at www.dwyer-inst.com for instructions on setting
up the meter parameters.
Notes: 1. The totalizer continues working in the background.
2. When selecting "no" for Total, the meter now functions as a
MPM Process Meter. We strongly
suggest that you download
and use the MPM instruction manual from our website
(www.dwyer-inst.com) while in this mode of operation.