Instruction manual

Analog Panel Meter Instruction Manual
28
Front Panel Buttons and Status LED Indicators
Button Description LED Status
Menu 1-8
Alarm 1 – 8 indicators.
Flashing with M Indicates
Manual Control Mode
Right arrow/F1 R Rate indicator
Up arrow/F2 T
Total indicator or
Flashing: Tare
Enter/F3 G T Grand Total indicator
Note:
F4 is a digital input. Alarms
5-8 are enabled when relay
expansion module is
installed.
Total overflow
indicator
M
Flashing: Manual control of
flashing relays. M flashing
alone indicates manual
analog output. Indicators
flash every 10 seconds.
Press the Menu button to enter or exit the Programming Mode at
any time.
Press the Right arrow button to move to the next digit during digit
or decimal point programming.
Press or hold the Up arrow button to scroll through the menus,
decimal point, or to increment the value of a digit.
Press the Enter button to access a menu or to accept a setting.
Press and hold the Menu button for three seconds to access the
advanced features of the meter.