Instruction manual
Analog Panel Meter Instruction Manual
12
RELAY RESET
User selectable via front panel buttons, digital inputs, or PC
1. Automatic reset only (non-latching), when the input
passes the reset point or total is reset to zero.
2. Automatic + manual reset at any time (non-latching)
3. Manual reset only, at any time (latching)
4. Manual reset only after alarm condition has cleared
(latching)
Note: Front panel button or digital input may be assigned to
acknowledge relays programmed for manual reset.
TIME DELAY
0 to 999.9 seconds, on & off relay time delays
Programmable and independent for each relay.
FAIL-SAFE
OPERATION
Programmable and independent for each relay.
Note: Relay coil is energized in non-alarm condition.
In case of power failure, relay will go to alarm state.
AUTO
INITIALIZATION
When power is applied to the meter, relays will reflect the
state of the input to the meter.
Isolated 4-20 mA Transmitter Output
OUTPUT
SOURCE
Rate/process, total, grand total, max, min, set points 1-8, or
manual control mode
SCALING RANGE
1.000 to 23.000 mA for any display range.
CALIBRATION
Factory calibrated: 4.000 to 20.000 = 4-20 mA output
ANALOG OUT
PROGRAMMING
23.000 mA maximum for all parameters:
Overrange, underrange, max, min, and break
ACCURACY
± 0.1% FS ± 0.004 mA
TEMPERATURE
DRIFT
0.4 µA/C max from 0 to 65C ambient,
0.8 µA/C max from -40 to 0C ambient
Note: Analog output drift is separate from input drift.
ISOLATED
TRANSMITTER
POWER SUPPLY
Terminals I+ & R: 24 VDC 10%. May be used to power the
4-20 mA output or other devices. Refer toFigure 5 on page
19 and Figure 15 on page 24.
All models rated @ 40 mA max.
EXTERNAL LOOP
POWER SUPPLY
35 VDC maximum
OUTPUT LOOP
RESISTANCE
Power supply Minimum Maximum
24 VDC
10 700
35 VDC (external)
100 1200