Specifications
10
Dutchwest
30003847
Clearances
As with any solid fuel heating stove, extremely high
surface temperatures can occur, particularly in the
event of uncontrolled operation, e.g. if the doors
are inadvertently left open. It is crucial that suf-
ficient clearances are allowed to any combustible
surfaces, e.g. wooden mantels or lintels, and to
timber framed (studded) walls even if they are faced
with noncombustible board. Detailed information
on fireplace and hearth construction is provided
in section 2 of Document J, all installations must
comply with these requirements or with the relevant
National or local building standards.
Clearances to timber framed (studded) walls are in-
cluded below. There are no specific minimum clearanc-
es to solid noncombustible surfaces (e.g. the sides and
rear of Inglenook fire openings constructed from solid
masonry) other than to allow safe access to the controls
of the stove. For this reason minimum side clearances
of 15 mm, and a minimum rear clearance of 50 mm
are recommended.
Summary of Clearances
Minimum recommended side clearances to non-
combustible surfaces 125 mm (5”).
Minimum recommended rear clearance to noncom-
bustible surfaces 50 mm (2”).
NOTE: The minimum thickness of solid noncombus-
tible materials is specified in section of Document ‘J’,
in relation to the clearance of the appliance from the
surface. As a general rule, the thickness of solid non-
combustible material forming the recess of a fireplace is
a minimum of 00 mm.
Minimum rear clearance from combustible walls
(e.g. timber framed or studded walls) 610 mm (24”)
for Models 2460CE and 900 mm (35C\,”) for Models
2461CE, 2462CE measured from the rear edge of
the stove top. (Fig. 13, B)
ST486a
Defiant EU
Clearance
Diagrams
10/06
A
B
ST486a
Fig. 13 Minimum clearances.
Minimum side clearance from combustible walls
610 mm (24”) for Model 2460CE and 700 mm (27Z\x”)
for Models 2461CE, 2462CE measured from the
side edge of the stove top. (Fig. 13, A)
Minimum distance from stove to movable combus-
tible materials (e.g. furniture, drying clothes, etc.)
1220 mm (48”).
Connecting Flue Pipe - Clearances
Single wall connecting fluepipes can reach extremely
high temperatures; therefore, clearances from the con-
necting fluepipe (chimney connector) must comply with
the requirements of Part J of Building Regulations 000
(Combustion Appliances and Fuel Storage Systems).
This can be achieved by following the recommenda-
tions of Approved Document ‘J’. These are as shown in
Figure 14.