Troubleshooting guide
17
through the access door while someone twist-locks the Pipe Section to it. Use
an Adjustable Pipe Length as needed to obtain a specific location for the
appliance. Make a mark on the horizontal Pipe Section flush with the vertical
face of the masonry, for referencing the vertical position. Slip a Pipe Collar
over the horizontal Pipe Section and install the remaining fittings as shown in
Figure 30. A minimum of 12 inches of connector rise is required.
(i). Insulation. Pull the Pipe Collar towards the 90° Elbow. Fill in the
gap between the masonry and the horizontal
Pipe Section with ceramic fiber insulation
or fiberglass, as shown in Figure 31. If
fiberglass is used, remove any paper
backing. The filling may be faced off with
grout, if desired. Push the Pipe Collar
back flush with the masonry. Make any
final adjustments on the Adjustable
Length Pipe (if used), and tighten the
clamping bolts.
TROUBLESHOOTING
1.  Purpose. This section is intended as a general maintenance and
troubleshooting guide, and as such, cannot encompass all configurations or vent
designs. For problems encountered which are beyond the scope of this sheet,
contact your Dura-Vent Dealer, Distributor, or Simpson Dura-Vent's Engineering
Department.  It is imperative that the one-inch clearance (air space) defined
in these instructions be maintained. In most cases, a one-inch minimum
clearance must be maintained to combustibles. The only exceptions are 4-inch, 5-
inch and 6-inch Oval B-vent which are installed within stud walls. Oval B-vent
and BW Vent are the subject of a separate installation instruction, and are not
discussed here. In these cases, the clearances are established by the listed Firestop
Spacers described in the instructions for Oval B-Vent.
2. Appliance. Read the appliance installation instructions carefully, insuring
that the prescribed clearances are met, and that it is a Category I appliance.
3. Spillage. Spillage from an appliance draft hood may cause condensation
on windows, or odors that the occupant may notice. Spillage may be caused
by an incorrectly sized vent system, blockage of the vent system, or a downdraft
in the vent. Other causes are: excessive lateral runs, too many elbows, improper
pitch to lateral runs (1/4 inch per foot of run is correct), fans or ventilation
systems in the same general area as the gas appliance, or wind conditions at the
CERAMIC
FIBER
INSULATION
Fig 31










