SECTION E - TERMINATIONS, STARTING ADAPTORS, DRAIN
LENGTH AND RELIEF VALVE
STARTING ADAPTORS
Single Wall Adaptor (SWA)
1. The Single Wall Adaptor is used as an appliance connector. It is de-
signed to be clamped with a Retaining Band and a locking band over
a shank type flue gas outlet.
2. First, slide the retaining band over the appliance outlet and tighten it
with supplied bolt. (See figure 38).
3. Add a bead of sealant about 1/8” on the flange of the retaining band
and one on the flange of the adaptor (SWA) and mate those two flanges
together. Be sure to fill all the gaps with S-2000 sealant. (See figure
39 and figure 40).
4. Tighten the Locking Band to hold and seal the adaptor in place. See
Figure 41 for typical installation.
ANSI Flange Adaptor (FA)
1. The Flange Adaptor (FA) is intended for use as a connection to a class
125 or 150 ANSI pipe flange.
2. This type of connection requires a flange gasket and bolt set provided
by the installer. The gasket and bolts are typically sold by pipe, valve
and fittings houses as ‘NBG’ set. Figure 42 illustrates a typical instal-
lation.
3. An outer band with insulation is included to close the installation.
Flanged Adaptor (FHA)
1. The Flanged Adaptor (FHA) is used to connect the DIS / DAS chimney
to flanged appliance outlets other than those with ANSI pipe flanges.
2. The adaptor is designed to sandwich an 1/2 inch flange between two
half ring and the appliance flanged outlet. The Flange Adaptor comes
with beam clamps to clamp the FHA to the appliance. See Figure 43.
DIS/DCT, DCT/DIS, DAS/DCT, DCT/DAS Adaptor
1. Used to connect model DIS / DAS chimney to model DCT chimney.
See Figure 44.
Figure 38 - Single wall adaptor
Figure 39
Figure 40
Figure 41
APPLIANCE
OUTLET
Insert and tighten
the band in place
APPLIANCE
OUTLET
Apply bead
of sealant
APPLIANCE
OUTLET
Insert the
coupling end
APPLIANCE
OUTLET
Tighten the
locking band
OTHER ADAPTORS
Female Single Wall Adaptor (FSWA)
1. The Female Single Wall Adaptor is used as a connector to specialised
component or existing chimney connection. It is designed to be
clamped with a Retaining Band and a locking band over a shank type
flue gas inlet.
2. First, slide the retaining band over the system inlet and tighten it with
supplied bolt. (See figure 38a).
3. Add a bead of sealant about 1/8” on the flange of the retaining band
and one on the flange of the adaptor (SWA) and mate those two flanges
together. Be sure to fill all the gaps with S-2000 sealant. (See figure
39a and figure 40a).
4. Tighten the Locking Band to hold and seal the adaptor in place. See
Figure 41a for typical installation.
Female ANSI Flange Adaptor (FFA)
1. The Female Flange Adaptor (FFA) is intended for use as a connection
to a class 125 or 150 ANSI pipe flange.
2. This type of connection requires a flange gasket and bolt set provided
by the installer. The gasket and bolts are typically sold by pipe, valve
and fittings houses as ‘NBG’ set. Figure 42 illustrates a typical instal-
lation.
3. An outer band with insulation is included to close the installation.
Figure 38a - Female Single wall
adaptor
Insert and tighten
the band in place
INLET
Figure 39a
INLET
Apply bead
of sealant
Insert the
coupling end
Figure 40a
Tighten the
locking band
INLET
Female Flanged Adaptor (FFHA)
1. The Flanged Adaptor (FFHA) is used to connect the DIS chimney to
flanged appliance outlets other than those with ANSI pipe flanges.
2. The adaptor is designed to sandwich an 1/2 inch flange between two
half ring and the appliance flanged outlet. The Flange Adaptor comes
with beam clamps to clamp the FFHA to the appliance. See Figure 43.
INLET
Figure 41a