Instruction
ATTIC
INSULATION
SHIELD
FIRESTOP
RADIATION
SHIELD
(INSIDE)
ENCLOSURE
MUST HAVE 2
INCHES OF
CLEARANCE
BETWEEN
CHIMNEY AND
WALL
FIRST
FLOOR
OCCUPIED
SECOND
FLOOR
ATTIC /
UNOCCUPIED
SPACE
5
manufacturer’s instructions and safety manual
in regards to fuels. Not all appliances are
equipped to burn coal. Coal with a low sulfur
content will reduce the possibility of corrosion.
Care must be taken to avoid over-ring, which
can damage the appliance, stovepipe and
chimney system.
Mobile Homes: Please read the appliance
manufacturer’s instructions and safety manual
carefully. Not all appliances are listed for use
in mobile homes.
CHIMNEY HEIGHT
The National Fire Protection Association
Standard #211 states: “Chimneys shall extend
at least three feet above the highest point
where it passes through the roof of a building,
and at least two feet higher than any portion
of a building within ten feet.” (Fig.1) DuraTech
Chimney may be installed up to 60 feet high. If
the chimney extends more than 5 feet above
the roof, an Extended Roof Bracket must be
used (see page 12). Due to the overlap of the
joints, subtract 1-1/4 inches from each Chimney
Section’s height to calculate installed height.
CHIMNEY PLACEMENT
When deciding the location of your chimney,
try to avoid modications to roof beams and
other structural components of the building.
CHIMNEY ENCLOSURE REQUIRE-
MENTS
Through Rooms: Interior chimneys shall be
enclosed where they extend through closets,
storage areas, occupied spaces, or any place
the surface of the chimney could be contacted
by persons or combustible materials. Maintain
at least a 2-inches of clearance between the
outer wall of the chimney and the enclosure
(Fig.2).
Figure 1
Figure 2
2 FT MIN ABOVE HIGHEST
POINT OF ROOF WITHIN
10 FT
10 FT
3 FT MIN
ABOVE
ROOF
Multi-Story: Consult local building codes for
requirements in your area. In the U.S., the
National Fire Protection Association Standard
#211 states: “Factory-built chimneys that
pass through oors of buildings requiring the
protection of vertical openings shall be enclosed
with approved walls having a re resistance