STEP 5: CONNECT SIGNAL CABLE
BEFORE PERFORMING ANY ELECTRICAL WORK, READ THESE REGULATIONS
1. All wiring must comply with local and national electrical codes and regulations, and must be
installed by a licensed electrician.
2. All electrical connections must be made according to the Electrical Connection Diagram
located on the panels of the indoor and outdoor units.
3. If there is a serious safety issue with the power supply, stop work immediately and contact
a licensed electrician. Do not continue with the installation until the safety issue is properly
resolved.
4. Power voltage should be within 90-110% of rated voltage. Insufficient power supply can cause
malfunction, electrical shock, or fire.
5. If connecting power to fixed wiring, install a surge protector and main power switch with a
capacity of 1.5 times the maximum current of the unit.
6. If connecting power to fixed wiring, a switch or circuit breaker that disconnects all poles and
has a contact separation of at least 1/8" (3mm) must be incorporated in the fixed wiring. A
qualified technician must use an approved circuit breaker or switch.
7. Only connect the unit to an individual branch circuit outlet. Do not connect another appliance
to that outlet.
8. Make sure to properly ground the air conditioner.
9. Every wire must be firmly connected. Loose wiring can cause the terminal to overheat,
resulting in product malfunction and possible fire.
10. Do not let wires touch or rest against refrigerant tubing, the compressor, or any moving parts
within the unit.
11. If the unit has an auxiliary electric heater, it must be installed at least 40" away from any
combustible materials.
12. To avoid getting an electric shock, never touch the electrical components soon after the
power supply has been turned off. After turning off the power, always wait 10 minutes or more
before you touch the electrical components.
4. Pass the drain pipe through the wall hole to the outside. The end of the pipe should be at least
2" (50mm) above the ground. If it touches the ground, the pipe may become blocked. Make
sure the water drains to a safe location where it will not cause water damage or a slipping
hazard.
WARNING
Ensure that the drain slope has a gradient of 1/100 or greater. Improper installation
can cause the drain pipe to back up into the unit and water leaks.
WARNING
Before performing any electrical or wiring work, turn off the main power to the
system.