Specification Sheet

2 Form No. V1.0_02.21
Specifications are subject to change without notice.
© 2021 Ferguson Enterprises LLC
www.durastar.com
12,000 BTU/H WALL MOUNTED HEAT PUMP SYSTEM
SYSTEM DATA
Refrigerant Type R-410A
Refrigerant Charge (oz.) 40.6
Oil Type Ester Oil VG74
Oil Charge (oz.) 12.5 (370 ml)
Design Pressure (PSIG) 550/340
LINE SET REQUIREMENTS
Connection Type Flare
Liquid Ø1/4" (Ø6.35mm)
Gas Ø1/2" (Ø12.7mm)
Pre-Charge Length 25'
Minimum Length 10'
Maximum Length 82'
Maximum Height Differential 33'
Additional Refrigerant (oz./ft) 0.16
SOUND PRESSURE (dB(A))
Indoor Unit
Low 25
Medium 30
High 36.5
Outdoor Unit
55
INDOOR UNIT DIMENSIONS
Unit Dimensions
Width 31 9/16"
Depth 7 7/16"
Height 11 11/16"
Carton Dimensions
Width 34 7/16"
Depth 11 1/4"
Height 14 15/16"
Net Weight
18.7 lbs.
Gross Weight
24.3 lbs.
OUTDOOR UNIT DIMENSIONS
Unit Dimensions
Width 31 1/2"
Depth 13 1/8"
Height 21 13/16"
Carton Dimensions
Width 36 1/4"
Depth 15 3/8"
Height 24 5/8"
Net Weight
80.5 lbs.
Gross Weight
86.2 lbs.
FAN DATA
Indoor Unit Air Flow (CFM)
Low 147
Medium 212
High 306
Moisture Removal (Pints/hr) 3.17
Drain Port O.D. / Drain Hose I.D. Ø5/8" (Ø16mm)
SPECIFICATIONS