Specification
Project Name/Project Number/26-Aug-15  07 65 00  (Masonry Accessories) Flexible Flashing 
    DuPont™ Thru-Wall Flashing 
© 2009 DuPont. DuPont™, and all products denoted herein with ™ or ® are trademarks or registered trademarks of E.I. 
du Pont de Nemours and Company. All rights reserved. 
5.  On interior, install backer rod in joint between frame of window and flashed rough framing. Apply 
sealant around entire window to create air seal. Apply sealant in accordance with sealant 
manufacturer’s instructions and ASTM C 1193. 
3.7 FIELD QUALITY CONTROL 
(Specifier Note: Field observation by a manufacturer designated representative is recommended for all projects 
using DuPont
™
 FlexWrap
™
. DuPont
™
 StraightFlash and DuPont
™
 StraightFlash
™
 VF) 
A. Notify manufacturer’s designated representative to obtain periodic observations of flexible flashing 
assembly installation. 
3.8 PROTECTION 
A. Protect installed flexible flashing from damage during construction. 
END OF SECTION 
DISCLAIMER: 
DuPont Building Innovations Guide Specifications have been written as an aid to the professionally qualified 
specifier and design professional. The use of this guideline specification requires the sole professional judgment 
and expertise of the qualified specifier and design professional to adapt the information to the specific needs for 
the building owner and the project, to coordinate with their construction document process, and to meet all the 
applicable building codes, regulations and laws. DUPONT EXPRESSLY DISCLAIMS ANY WARRANTY, 
EXPRESSED OR IMPLIED, INCLUDING THE WARRANTY OF MERCHANTABILITY OR FITNESS FOR 
PARTICULAR PURPOSE OF THIS PRODUCT FOR THE PROJECT. 
Please contact your local DuPont
™
 Tyvek
®
 Specialist at 1-800-44-Tyvek or visit www.construction.tyvek.com 