INFORMATION MODE
Press [MODE] button 2 times from Standby Mode.
Display shows Info until a key is
pressed
Info Then displays Parameter, Flashing Dot, and Current Status.
1.190
Press and Hold Key(s) in BLACK (1) Duration Result Display
[MODE] [STEP] [STORE] [+] [-] Tap
Step to next
parameter
Measured outlet water temperature
(First digit shows 1 and dot ashes) (1)
1.180
(1) Digits after ashing dot show measured outlet temperature.
(2) Digits after ashing dot show -18.
(3) Digits after ashing dot show outside temperature.
(4) Digits after ashing dot show target outlet temperature.
(5) Digits after ashing dot show rate of change in °F per second.
(6) Digits after ashing dot show -32.
NOTE: Display will show A-32 if [STEP] is pressed after “9” appears.
Return water temperature
(First digit shows 2 and dot ashes) (1)
2.150
This function not used
(First digit shows 3 and dot ashes) (2)
3.-18
Outside temperature
(First digit shows 4 and dot ashes) (3)
4. 42
This function not used
(First digit shows 5 and dot ashes) (2)
5.-18
Target outlet water temperature
(First digit shows 6 and dot ashes) (4)
6.190
Outlet water temp. change over time
(First digit shows 7 and dot ashes) (5)
7. 1
Return water temp. change over time
(First digit shows 8 and dot ashes) (5)
8. 1
This function not used
(First digit shows 9 and dot ashes) (6)
9.-32