BOILER RATINGS AND CAPACITIES
Table 1 - Ratings and Capacities
BOILER MODEL NUMBER
(1)
No. of
Sections
†Natural Gas †Propane Gas Dimensions
(Inches)
Intermittent
Ignition w/
Vent Damper
Standing
Pilot
w/Vent
Damper
Input
*MBH
Heating
Capacity
*MBH
Net
I=B-R
Rating
*MBH
Net
I=B=R
Rating Sq.
Ft.
Input
*MBH
Heating
Capacity
*MBH
Net
I=B=R
Rating
*MBH
Net
I=B=R
Rating
Sq. Ft.
Radiation
Flue
Diameter
"A"
Width
PSB-3D PVSB-3D 3 75 62 47 196 70 58 44 183 5 11¼
PSB-4D PVSB-4D 4 112.5 91 68 283 105 85 64 267 6 14½
PSB-5D PVSB-5D
5
150 122 92 383 140 114 86 358 6 17¾
PSB-6D PVSB-6D 6 187.5 153 115 479 175 143 107 446 7 21
PSB-7D PVSB-7D 7 225 183 137 571 210 171 128 533 7 24¼
PSB-8D PVSB-8D 8 262.5 214 161 671 245 200 150 625 7 27½
PSB-9D PVSB-9D 9 299 245 184 767 280 229 172 717 7 30¾
* MBH = 1,000 Btuh. Btuh = British Thermal Unit Per Hour.
** Add 5½" to height for Vent Damper
† For altitudes above 2,000 ft. reduce input rate 4% for each 1,000 ft. above sea level.
Heating Capacity is based on DOE (Department of Energy) test procedure.
(1)
Add model number suf x 'P' for Propane Gas.
The net I=B=R steam Ratings shown are based on a piping
and pickup allowance of 1.333.
Base selection of boiler size on "Net I=B=R Rating"
being equal to or greater than installed radiation in
square feet. Consult manufacturer before selecting a
boiler for installations having unusual piping and pickup
requirements,such as intermittent system operation,
exhaust piping systems, etc.
Speci cations and dimensions are subject to change
without notice.