GAS SUPPLY PIPING
CAUTION
WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use
any phone in your building.
• Immediately call your gas supplier from a
neighbor’s phone. Follow gas supplier’s
instructions.
• If you cannot reach your gas supplier, call the re
department.
!
General
• Use piping materials and joining methods acceptable
to authority having jurisdiction. In absence of such
requirements National Fuel gas Code, ANSI Z223.1/
NFPA 54.
• Size and install gas piping system to provide sufcient
gas supply to meet maximum input at not less than
minimum supply pressure.
See Tables 4a and 4b.
Table - 4a Gas Pipe Sizes - Natural Gas
Length
of Pipe
- Ft.
Pipe Capacity - BTU Per Hour Input
Includes Fittings
1/2" 3/4" 1" 1 -1/4"
20 92,000 190,000 350,000 625,000
40 63,000 130,000 245,000 445,000
60 50,000 105,000 195,000 365,000
Table - 4b Gas Pipe Sizes - Propane Gas
Length
of Pipe
- Ft.
Pipe Capacity - BTU Per Hour Input
Includes Fittings
5/8" 3/4" 1/2" 3/4"
20 131,000 216,000 189,000 393,000
40 90,000 145,000 129,000 267,000
60 72,000 121,000 103,000 217,000
* Outside diameter
Length of pipe or tubing should be measured from the gas meter
or propane second stage regulator.
• Support piping with hooks straps, bands, brackets,
hangers, or building structure components to prevent or
dampen excessive vibrations and prevent strain on gas
connection. Gas valve will not support piping weight.
• Use thread (joint) compound (pipe dope) suitable for
natural and liqueed petroleum gas.
• Install eld sourced manual main shutoff valve, ground
joint union, and sediment trap upstream of gas valve.
See Figure 11.
DANGER
Fire Hazard. Do not use matches, candles, open
ames, or other methods providing ignition source.
Failure to comply will result in death or serious
injury.
!
Leak Check Gas Piping
Pressure test boiler and gas connection before placing
boiler in operation. Avoid excessive pressure that could
damage pressure regulators, valves, or meters.
•
Pressure test at 1/2 psig (3.5 kPa) or less. Isolate
boiler from gas supply system by closing manual gas
shutoff valve.
•
Locate leakage using gas detector, noncorrosive
detection uid, or other leak detection method
acceptable to authority having jurisdiction. Do not
use matches, candles, open ames, or other methods
providing ignition source.
•
Correct leaks immediately and retest.
Figure 11 - Gas Piping At Boiler
3” Minimum
Sediment
Trap
Manifold
Floor Line
Automatic
Gas Valve
Ground
Joint
Union
Propane Installation
WARNING
Fire, explosion, asphyxiation hazard. Verify boiler
is equipped with propane gas orices and gas valve
is congured for propane. Failure to follow these
instructions may result in serious injury or death.
•
Connections by licensed propane dealer only.
•
Use two stage regulator provided by propane
supplier.
•
Have propane supplier check piping.