User Manual

45
Remove ¼-20 hex ange nuts securing condensate
collector to heat exchanger using 7/16" deep well
socket. See gures 11-3 & 11-4.
Remove condensate collector assembly from heat
exchanger and ue pipe.
Flush collector and condensate trap with water.
Follow Burner Inspection Kit instructions to reassemble
boiler and resume operation.
11 - GENERAL MAINTENANCE AND CLEANING