Owner's manual
9
Specifi c Parameters Level
(Default) Value Range
°C °F °C °F
Permit Boiler Emergency Mode [-] 1: User yes yes/no
Cascade CH Setpoint
[ºC/ºF]
1: User
80 160 40..93 104..200
Boiler Address [-] 2: Installer 0 0..15 0..15
Cascade Emergency Setpoint [ºC/ºF] 2: Installer 45 113 20..65 68..149
Start Delay Time [min] 2: Installer 3 1..15
Stop Delay Time
[min] 2: Installer 3 1..15
Start Boiler Diff [ºC/ºF] 2: Installer 5 9 0..20 0..36
Stop Boiler Diff [ºC/ºF] 2: Installer 2 18 0..20 0..36
Calculated setpoint Max offset down
[ºC/ºF]
2: Installer 4 36 0..20 0..36
Calculated setpoint Max offset up [ºC/ºF] 2: Installer 10 18 0..20 0..36
Start Modulation Delay Factor [-] 2: Installer
5
0=disabled
1..60
Next Boiler Start Rate [%] 2: Installer 80 10..100
Next Boiler Stop Rate [%] 2: Installer 30 10..100
Rotation Interval [days]
2: Installer 1
0..30
0=disabled
Boilers for DHW [-]
2: Installer all All,1..16
Not
available
System Pump - Post Pump Time [sec] 2: Installer 30 seconds 1…90
MULTIPLE BOILER GUIDE