A6. Set The Stainless Condensing Boiler CH
6-1. Set stainless Condensing boiler to be Master boiler
in Cascade mode. Change S4-switch to ON posi-
tion, (away from S4 mark on control board). See
Figure A5.
6-2. Change boiler address to Cascade 1 following
procedure below.
Press down and hold “Enter” button and
immediately press down and hold “Menu” button
for 5 seconds to enter into Installer Menu.
Use arrow keys to go to “Boiler Cong”
Press “Enter” key
Press “Enter” key again. The number after
“Boiler Address:” will be ashing.
Use arrow keys to change this number to 1.
Press “Enter” key, number will stop ashing.
Press “Menu” key twice to exit Installer Menu.
CASCADE 1 should appear on user interface.
6-3a Set System Temperature Setting for Stainless
Condensing boiler. If outdoor reset is activated
(CH Mode 1 or CH Mode 2) and if heating system
requires a reset curve different from the default
curve.
Change Outdoor Reset curve. Detailed
instructions can be found in boiler Installation,
Operation and Maintenance Manual (IOM).
Set “Boiler Max” parameter to about 20°F lower
than setting point of Additional Heating Device,
i.e. 150°F.
6-3b If outdoor reset function is deactivated (CH
mode 0), follow procedure below to set System
Temperature Setting point.
Press “Menu” button.
Scroll down to “Setting” using arrow keys.
Press “Enter” key.
Press “Enter” key again. The number after
“Cascade CH Setting” will be ashing.
Use arrow keys to change this number to about
20°F lower than setting point of Additional
Heating Device, i.e. 150°F.
Press “Enter” key. Number will stop ashing.
Press “Menu” key twice to exit setting mode.
A7. Set The Stainless Condensing Boiler DHW Setting
7-1 Set DHW supply temperature setting of stainless
condensing boiler to temperature about 10°F lower
than corresponding DHW setting point on Additional
Heating Device, i.e. 170°F.
A8. Create CH call for heat and verify system works
as intended.
A9. Create DHW call for heat, if applicable, and verify
system works as intended.
SECTION A - STAINLESS CONDENSING BOILER OPERATING WITH HIGH TEMPERATURE HEATING DEVICE