12.1 Antifreeze added to boilers must be nontoxic,
and must be of type specically intended for use in closed
hydronic heating systems. Under no circumstances should
automotive antifreeze be used. Antifreeze used in any
boiler may reduce capacity by 10% or more and increase
fuel consumption. See Table 6 and 7.
Table 6 - BOILER WATER VOLUMES
Number of
Boiler Section
Total Volume
(Gallons)
4 3.6
5 4.3
6 5.1
7 5.9
Table 7 - PIPING WATER VOLUMES
PIPE SIZE
COPPER
PIPE
FACTOR
STEEL PIPE
FACTOR
½” 82.5 63.5
¾” 40.0 36.0
1” 23.3 22.2
1 ¼” 15.3 12.8
1 ½” 10.8 9.5
2” 6.2 5.8
Divide total length of piping in feet by
appropriate factor in table to determine volume
in gallons.
12 - ANTIFREEZE IN THE SYSTEM